Technibel CAFP 124 R Technical Data & Service Manual page 132

Package air conditioner dc inverter r410a
Hide thumbs Also See for CAFP 124 R:
Table of Contents

Advertisement

List of Item Codes
Item code
01
Control system schedule
02
Control system schedule
03
Control system schedule
04
Snowfall sensor operation
05
Outdoor fan quiet mode
06
Defrost fan speed selection
07
Ignore capacity
08
Control system schedule
09
Control system schedule
0A
Control system schedule
0b
Control system schedule
0C
Forced operation of
indoor unit drain pump
0d
Odor countermeasure when
indoor cooling thermostat is OFF
0E
Cool only
0F
Control system schedule
10
Control system schedule
5
11
Multi-floor installation
12
Control system schedule
13
Control system schedule
50
Demand 1
51
Demand 2
52
Current control level
Parameter
0 = No sensor, control performed
1 = No sensor, control not performed
2 = Sensor present, control performed
3 = Sensor present, control not performed
0 = Disabled
1 = Quiet mode
0 = Disabled
1 = LL fan speed
(This function is not present with the DC-INV.)
0 = Disabled
1 = Ignores capacity ratio
0 = Disabled
1 = During cooling only, 2 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
2 = During cooling only, 4 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
3 = At all times, 4 hours stopped + 20 minutes operating
4 = At all times, 2 hours stopped + 20 minutes operating
0 = Disabled
1 = Odor countermeasure is active
0 = Heat pump
1 = Cool only
0 = No
1 = Yes
40%, 45% ... 100% ... 160%
40%, 45% ... 100% ... 160%
40%, 45% ... 100% ... 160%, –1 (no control)
* Figures in parentheses indicate the data at the time of shipment from the factory.
5 - 8