How To Use The Vent Graph - Monessen Hearth KHLDV400 Install And Operation Instructions

Khldv series direct vent gas fireplace
Table of Contents

Advertisement

KHLDV Series Gas Fireplace
terMInatIOn cLearanceS FOr BuILDInGS wItH cOMBuStIBLe
anD nOncOMBuStIBLe exterIOrS
G
G=6" (152mm)
V
Combustible – 6" (152 mm)
Noncombustible – 2" (51mm)
Inside Corner
G
V
G = Combustible 24"(610mm)
Noncombustible 18"(457mm)
Balcony with No Side Wall
Figure 9 -
Allowable Venting Chart

HOw tO uSe tHe Vent GrapH

The Vent Graph should be read in conjunction with the
following vent installation instructions to determine the
relationship between the vertical and horizontal dimensions
of the vent system.
1. Determine the height of the center of the horizontal vent
pipe exiting through the outer wall. Using this dimen-
sion on the Sidewall Vent Graph below, locate the point
intersecting with the slanted graph line.
2. From the point of this intersection, draw a vertical line
to the bottom of the graph.
3. Select the indicated dimension, and position the fire-
place in accordance with same.
Example: If the vertical dimension from the floor of the
fireplace is 11' (3.4 m) the horizontal run to the face of
the outer wall must not exceed 16' (4.9 m).
Sidewall Vent Graph showing the relationship between
vertical and horizontal dimensions for a Direct Vent flue
system.
14
V
F
F=6" (152mm)
Outside Corner
H
V
J
Combustible &
Noncombustible
H = 24" (610mm)
J = 20" (508mm)
Balcony with Perpendicular
Side Wall
FP1951
termination clearances
Figure 10 -
Rear Wall Venting Graph
VentInG InStaLLatIOn
C = Maximum depth of 48" (1219mm)
for alcove location
D = Minimum width for back wall of
alcove location
Combustible - 38" (965mm)
Noncombustible - 24" (610mm)
E = Clearance from corner in alcove
location
Combustible - 6" (152mm)
Noncombustible - 2" (51mm)
Alcove Location
Dimensions in
Feet
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
2  4  6  8 10 12  1 4 16 18  2 0
Horizontal dimension from the finished outside wall
to the center of the pipe on the fireplace
FP2132
sidewall vent graph
D
C
V
E
eg: A
73D0024