7.

ADDITIONAL CHARGE CALCULATION

MODEL : AOU36RLXFZ
Refrigerant type
Refrigerant amount
Refrigerant charge
●3 or 4 indoor units are connected
Total pipe length
Additional charge
●2 indoor units are connected (with optional parts K9FZ1818)
Total pipe length
Additional charge
R410A
lbs. oz.
7 lbs. 4 oz.
g
3300
ft.
164 or less
197
m
50 or less
60
lbs. oz.
0
8.9 oz.
g
0
250
ft.
65 or less
98
m
20 or less
30
lbs. oz.
0
8.9 oz.
g
0
250
- (04 - 36) -
230 (MAX)
70 (MAX)
0.27 oz./ft.
25 g/m
1 lb. 1.8 oz.
500
131 (MAX)
40 (MAX)
0.27 oz./ft.
25 g/m
1 lb. 1.8 oz.
500