INSTALLATION
Connection Pattern
Note: Connection pattern is different according to type of Indoor unit.
Indoor unit types
Compact Cassette type
Slim Duct type
Compact Wall Mounted type
Wall Mounted type
Pattern A
Connect the end of remote controller cable directly to the exclusive terminal block.
M4 screw
Terminal block
Note: It may be failed if it is connected to the outdoor unit or the terminal block for power
supply.
Pattern B
1) Modify the remote controller cable as per below methods.
Use a tool to cut off the terminal on the end of the remote controller cable and then remove
the insulation from the cut end of the cable as shown in Fig.
Connect the remote controller cable and connecting cable as shown in Fig.
Be sure to insulate the connection between the cables.
Remote controller
cable
2) Method of connecting remote controller cable
Connecting cable made by above-mentioned 1) is connected with terminal (CN305) of
optional communication kit (UTY-XCBXZ1).
Cable connected with terminal (CN301) of communication kit (UTY-XCBXZ1) is connected
with PCB of Indoor unit.
Connecting
cable
Remote controller
cable
Connection Pattern
Pattern A
Pattern B
Pattern C
Remote controller
Remote
terminal block
controller
cable
Connecting
cable
White
Red
Black
White
Red
Insulated
connection
Black
Terminal
(CN301)
Terminal
(CN305)
Communication kit
(UTY-XCBXZ1)
- (01 - 15) -
Outdoor unit /
Power supply
terminal block
Indoor unit
PCB
Indoor unit PCB