Boiler Ratings And Capacities - Dunkirk PSB-3D Installation, Operation & Maintenance Manual

Plymouth steam series 2 gas-fired steam boilers
Table of Contents

Advertisement

Figure 1 - Dimensions
BOILER MODEL NUMBER
(1)
Standing
Intermittent
Sections
Pilot
Ignition w/
w/Vent
Vent Damper
Damper
PSB-3D
PVSB-3D
PSB-4D
PVSB-4D
PSB-5D
PVSB-5D
PSB-6D
PVSB-6D
PSB-7D
PVSB-7D
PSB-8D
PVSB-8D
PSB-9D
PVSB-9D
* MBH = 1,000 Btuh. Btuh = British Thermal Unit Per Hour.
** Add 5½" to height for Vent Damper
† For altitudes above 2,000 ft. reduce input rate 4% for each 1,000 ft. above sea level.
Heating Capacity is based on DOE (Department of Energy) test procedure.
Add model number suffi x 'P' for Propane Gas.
(1)
The net I=B=R steam Ratings shown are based on a piping
and pickup allowance of 1.333.
Base selection of boiler size on "Net I=B=R Rating"
being equal to or greater than installed radiation in
square feet. Consult manufacturer before selecting a
boiler for installations having unusual piping and pickup
requirements,such as intermittent system operation,
exhaust piping systems, etc.

BOILER RATINGS AND CAPACITIES

Table 1 - Ratings and Capacities
†Natural Gas
No. of
Heating
Input
Capacity
*MBH
*MBH
3
75
62
4
112.5
91
150
122
5
6
187.5
153
7
225
183
8
262.5
214
9
299
245
Net
Net
I=B-R
I=B=R
Input
Rating
Rating Sq.
*MBH
*MBH
Ft.
47
196
70
68
283
105
92
383
140
115
479
175
137
571
210
161
671
245
184
767
280
Specifi cations and dimensions are subject to change
without notice.
4
†Propane Gas
Net
Net
Heating
I=B=R
I=B=R
Capacity
Rating
Rating
*MBH
Sq. Ft.
*MBH
Radiation
58
44
183
85
64
267
114
86
358
143
107
446
171
128
533
200
150
625
229
172
717
Dimensions
(Inches)
Flue
"A"
Diameter
Width
5
11¼
6
14½
6
17¾
7
21
7
24¼
7
27½
7
30¾