1.6.2

Connection of the high power factor converter (FR-HC)

When connecting the high power factor converter (FR-HC) to suppress power supply
harmonics, perform wiring securely as shown below. Incorrect connection will damage
the high power factor converter and inverter.
R
S
NFB
Power
supply
CAUTION
1. Use sink logic (factory setting) when the FR-HC is connected. The FR-HC
cannot be connected when source logic is selected.
2. The power input terminals R, S, T must be open. Incorrect connection will
damage the inverter. Opposite polarity of terminals N, P will damage the
inverter.
3. The voltage phases of terminals R, S, T and terminals R4, S4, T4 must be
matched before connection.
4. Use Pr. 60 to Pr. 63 (input terminal function selection) to assign the terminals
used for the RES and MRS signals.
5. Do not insert NFB between terminals P-N (P - P, N - N)
6. The N terminal is not provided for the FR-S520E-0.1K to 0.75K.
High power factor converter (FR-HC)
(Caution 2)
T
R4
S4
T4
MC1 MC2
R4
S4
T4
From FR-HCL02
R3
S3
T3
MC2
External box
MC1
S2
R2
T2
FR-HCL01
R
S
T
(Caution 2)
Connection to the Stand-Alone Option
N
P
Y1 or Y2
RDY
39
Inverter
RSO
SE
R
S
(Caution 2)
T
SD
(Caution 1)
RES (Caution 4)
MRS (Caution 4)
(Caution 5)
P
N (Caution 6)
1