Mitsubishi FR-S500 Instruction Manual page 137

Transistorized inverter 3.7k-na / 0.75k-na
Hide thumbs Also See for FR-S500:
Table of Contents

Advertisement

Changing example Deflecting the meter (analog indicator) to full-scale (5V) at the
POINT
The calibration parameters "C1" can be made to be ready by setting "1" (extended
function parameter valid) in Pr. 30 "extended function display selection".
Set the value of the calibration parameter C1 "AM terminal calibration".
Operation
1.
Press the
MODE
parameter setting mode.
2.
Turn the
"
" .
Pr. 30 must be set to "1".
(For details, refer to the instruction
manual (basic).)
3.
Press the
SET
"
" .
4.
Turn the
calibration parameter C1 "
terminal calibration" appears.
5.
Press the
SET
6.
If the inverter is at a stop, press the
to start it. (The motor
RUN
need not be connected.)
7.
Turn the
indicator needle to the
desired position.
8.
Press the
SET
Setting is complete.
REMARKS
Depending on the set value, it may take some time for the needle to move.
If "1" is set in Pr. 30 "extended function display selection", the calibration parameter C1 "AM
terminal calibration" can also be set in the external operation mode.
When the FR-PU04 is used, make calibration with Pr. 901.
preset frequency of 60Hz (for frequency setting, refer to the
instruction manual (basic).)
to choose the
to show
to show
until the
AM
to enable setting.
to adjust the
.
By turning the
, you can read another parameter.
Press the
to return to the
SET
Press the
twice to show the next parameter (
SET
MODE
SET
SET
RUN
+
-
SET
Flicker ... Parameter setting complete!!
indication (step 3).
127
Calibration parameters
Display
The parameter
number read
previously
appears.
RUN
PU
EXT
Analog indicator
).
2