Setting Dial Function Selection (Pr. 53 ) - Mitsubishi FR-S500 Instruction Manual

Transistorized inverter 3.7k-na / 0.75k-na
Hide thumbs Also See for FR-S500:
Table of Contents

Advertisement

2.6.2
Setting dial function selection (Pr. 53
You can use the dial like a potentiometer to perform operation.
Parameter
Name
Frequency setting
53
operation selection
Using the setting dial like a potentiometer to perform operation
POINT
Set "1" (extended function parameter valid) in Pr. 30 "extended function display
selection".
Set "1" (setting dial potentiometer mode) in Pr. 53 "frequency setting operation
selection".
Operation example Changing the frequency from 0Hz to 60Hz during operation
1.
Mode/monitor check
Choose monitor/frequency monitor. (
The inverter must be in the PU operation mode.
(Press the
Pr. 30 must be set to "1".
Pr. 53 must be set to "1".
2.
Press the
RUN
3.
Turn the
clockwise until
appears. The flickering frequency is
"60.0"
the set frequency.
You need not press the
REMARKS
If flickering "60.0" turns to "0.0", the Pr. 53 "frequency setting operation selection" setting
may not be "1".
Independently of whether the inverter is running or at a stop, the frequency can be set by
merely turning the dial.
When the frequency is changed, it will be stored as the set frequency after 10s.
Refer to
Factory
Setting
0
Operation
PU
.)
EXT
to start the inverter.
.
SET
(page 90).
Display function parameters
Setting
Range
0: Setting dial
frequency setting
0, 1
mode
1: Setting dial
potentiometer mode
)
MODE
RUN
91
)
Remarks
Setting is
enabled when
Pr. 30 = "1"
Display
RUN
PU
EXT
RUN
PU
EXT
Flickers for 3s.
2