[when] 2011-06-09-21:26:38.331
[occurrences] 1
[set]
[what] Fiber signal is missing
[when] 2012-01-01-00:02:31.457
[OK] 2013-08-13T18:52:15Z
If the following alarm is active, use the settings fiber_mode command to verify the correct setting
and change as necessary to match the configuration of the upstream 4372A module (the 4372A
module requires ATS 6511 legacy mode, 4372A-T requires two-way or two-way disabled mode).
[fiber_signal_present]
[occurrences] 1
[set]
[what] Fiber is missing or not receiving timecodes (check upstream fiber mode)
[when] 2013-01-23-16:39:09.016
[outputs_disabled]
[occurrences] 1
[set]
[what] Outputs are disabled
[when] 2013-01-23-16:39:09.080

6.2.3 Outputs Enabled

This indicator will turn off if the ATS-6511 detects a hardware fault with one or more of the
output modules.
Verify the output modules outputs are good using the status
health:outputs_disabled command and verify active = false and occurrences = 0.
ATS-6511>status health:outputs_disabled
[active] false
[occurrences] 0
Users can determine which output module(s) has failed:
Based on which systems the ATS-6511 is driving are no longer operating properly
By using the status health:output_modules command and/or the syslog error command
and checking both the active = true and/or occurrences is greater than 0.
ATS-6511>status health:output_modules
[1]
[active] true
[occurrences] 1
[2]
[active] false
[occurrences] 0
[3]
[active] false
[occurrences] 0
[4]
[active] false
[occurrences] 0
[5]
[active] false
[occurrences] 0
[6]
If a card is not installed on a slot, that slot will not be
reported as part of the status message.