FLUE INSTALLATION

09:59
Page 22
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR UTILITY 32/50 & 50/708 716
FLUE INSTALLATION
The flue can exit the boiler from outlets A, B, C
or D allowing vertical (RS &CF) and horizontal
(RS low or high level) flues to be fitted. (CF
position 'A' only).
Refer to the separate flue installation
instructions supplied with the flue kits available
for this boiler:
RS FLUE KITS & COMPONENTS
Greenstar Oilfit 100/150mmØ (not supplied):
Horizontal flue kit: Part No. 7 716 190 043
Vertical flue kit: Part No. 7 716 190 044
Extension kit (1 metre) x1: Part No. 7 716 190 045
Inline elbow 90° x1: Part No. 7 716 190 046
Inline elbow 45° x2: Part No. 7 716 190 047
CF FLUE KITS & COMPONENTS:
Greenstar Oilfit 103mmØ (not supplied):
CF flue kit 130mmØ: Part No. 7 716 190 049
FLUE TERMINAL GUARD (not supplied):
Terminal Guard: Part No. 7 716 190 050
INSTALLATION NOTES:
Ensure all flue seals are in good condition
and seated properly.
To ease assembly of flue components,
grease seals lightly with the solvent-free
grease.
Use flue clamps, where supplied, to support
the flue system.
IMPORTANT: The boiler is not designed to
take the weight of the flue system, this
must be supported externally to the boiler.
All horizontal flue sections must rise by at
least 52mm for each metre away from the
boiler to ensure that condensate flows back
into the boiler for safe discharge via the
condensate waste pipe.
The horizontal terminal must be installed at
3° to ensure that the condensate drains
back to the boiler whilst also preventing rain
ingress down the air duct.
A flue terminal guard must be fitted if the
flue outlet is below 2 metres from the
ground level.