1. COOLING OPERATION

1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 4°F(2°C) higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is 5°F(2.5°C) lower than a set temperature, the compressor will be
stopped.
* When the room temperature is between +4°F(+2°C) to -5°F(-2.5°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure1 based on the
fan speed mode and the outdoor temperature.
( Table1 : Compressor Frequency Range )
ASU18RLF
ASU24RLF
( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outside air
temperature
A zone
93.2°F
(34°C)
B zone
86°F
(30°C)
C zone
66.2°F
(19°C)
D zone
50°F
(10°C)
E zone
32°F
(0°C)
F zone
minimum
maximum
frequency
frequency
12rps
55rps
16rps
72rps
Outside air
temperature
96.8°F
(36°C)
89.6°F
(32°C)
69.8°F
(21°C)
53.6°F
(12°C)
35.6°F
(2°C)
Hi
18RLF
A zone
55rps
B zone
55rps
C zone
47rps
D zone
37rps
E zone
37rps
F zone
37rps
24RLF
A zone
72rps
B zone
72rps
C zone
55rps
D zone
43rps
E zone
43rps
F zone
41rps
01-01
Me
Lo
Quiet
36rps
29rps
25rps
36rps
29rps
25rps
36rps
29rps
25rps
33rps
26rps
20rps
33rps
26rps
20rps
33rps
26rps
20rps
49rps
41rps
29rps
49rps
41rps
29rps
41rps
36rps
29rps
36rps
31rps
20rps
36rps
31rps
20rps
36rps
31rps
20rps