8. COMPRESSOR CONTROL

1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the table8.
(Table8 : Compressor Operation Frequency Range)
ASU18RLF
ASU24RLF
2. OPEARTION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the Figure9.
(Fig.9 : Compressor Control at Start-up)
60rps
47rps
30rps
Cooling
Min
Max
12rps
55rps
16rps
72rps
60sec
120sec
Heating
Min
Max
14rps
67rps
16rps
90rps
180sec
01-08
Dry
Min
Max
15rps
25rps
16rps
29rps