Indoor Fan Control - Fujitsu ASU18RLF Service Instructions Manual

Split type room air conditioner wall mounted type inverter
Hide thumbs Also See for ASU18RLF:
Table of Contents

Advertisement

5. INDOOR FAN CONTROL

1. Fan speed
( Table4 : Indoor Fan Speed )
Operation mode
Heating
Cooling/ Fan
Dry
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,
while the indoor fan only runs.
When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure3.
On the other hand, if switched in [HIGH]
operation modes QUIET, LOW, MED, HIGH,as shown in Table4.
( Fig.3 : Airflow change - over ( Cooling : AUTO ) )
TR-Ts > 4°F
4°F > TR-Ts > 2°F
(2°C)
2°F > TR-Ts
(1°C)
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool air prevention
S-Lo
Hi
Me
Lo
Quiet
HIGH mode
(2°C)
MED mode
=
(1°C)
LOW mode
When the room
temperature drops
Speed (rpm)
ASU18RLF
ASU24RLF
1260
1530
1120
1320
1020
1220
900
1020
790
900
680
720
270
270
1260
1480
1020
1220
900
1020
770
900
X zone : 770
X zone : 900
J zone : 720
J zone : 850
[QUIET], the indoor motor will run at a constant airflow of [COOL]
TR-Ts > 5°F
5°F > TR-Ts > 3°F
(2.5°C)
3°F > TR-Ts
(1.5°C)
When the room
temperature rises
TR : Room temperature
Ts : Setting temperature
01-04
=
(2.5°C)
=
(1.5°C)