Laars MagnaTherm MGH1600 Installation And Operation Instructions Manual page 92

Modulating boiler & water heater
Table of Contents

Advertisement

Page 88
Code
Description
225
Invalid Flame threshold setting
226
Invalid Outlet high limit setpoint setting
227
Invalid DHW (Domestic Hot Water)
high limit setpoint setting
228
Invalid Stack limit setpoint setting
229
Invalid Modulation output setting
230
Invalid CH (Central Heat) demand
source setting
231
Invalid Delta T limit delay setting
232
Invalid Pressure sensor type setting
234
Invalid Outlet high limit enable setting
235
Invalid Outlet connector type setting
236
Invalid Inlet connector type setting
Lockout
Procedure
or Hold
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.