Laars MagnaTherm MGH1600 Installation And Operation Instructions Manual page 88

Modulating boiler & water heater
Table of Contents

Advertisement

Page 84
Code
Description
164
Block intake ON
165
Block intake OFF
172
Main relay feedback incorrect
174
Safety relay feedback incorrect
175
Safety relay open
176
Main relay ON at safe start check
178
Safety relay ON at safe start check
184
Invalid BLOWER/ HSI output setting
185
Invalid Delta T limit enable setting
186
Invalid Delta T limit response setting
Lockout
Procedure
or Hold
L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it
is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the
voltage across the switch. Supply voltage should
be present. If not, the Block Intake Switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it
is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the
voltage across the switch. Supply voltage should
be present. If not, the Block Intake Switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
LAARS Heating Systems