LA NORDICA TermoSuprema Compact DSA Instructions For Installation, Use And Maintenance Manual page 28

Hide thumbs Also See for TermoSuprema Compact DSA:
Table of Contents

Advertisement

Available languages

Available languages

50 cm
2 m
1
m
CHIMNEY POT DISTANCES AND POSITIONING:
Roof slope
α α α α
15°
30°
45°
60°
28
10 m
>A
min. H
(1)Ridge axis
α
Distance between ridge and
chimney
A (m)
< 1.85 m
> 1.85 m
< 1.50 m
> 1.50 m
< 1.30 m
> 1.30 m
< 1.20 m
> 1.20 m
Thermocooker – TERMOSUPREMA Compact DSA
(1) If there are flues which are side by side, one
chimney pot must surpass the other by at least 50
cm in order to avoid pressure transfers between the
flues themselves.
(1) The chimney pot must not have obstacles within 10 m such
as walls, slopes or trees. If this is not the case, raise the pot by
at least 1 m above the obstacle.
The chimney pot must surpass the roof ridge by at least 1 m.
> _ A
0.5 m
(2)Roof
Minimum chimney height (measured from the
Instructions for installation, use and maintenance – EN – Rev.01
UNI 10683/98
outlet)
H (m)
0.50 m beyond the ridge
1.00 m from the roof
0.50 m beyond the ridge
1.30 m from the roof
0.50 m beyond the ridge
2.00 m from the roof
0.50 m beyond the ridge
2.60 m from the roof
Picture 7
Picture 8
Picture 9