Closed Expansion Vessel System - LA NORDICA TermoSuprema Compact DSA Instructions For Installation, Use And Maintenance Manual

Hide thumbs Also See for TermoSuprema Compact DSA:
Table of Contents

Advertisement

Available languages

Available languages

1.
OPEN EXPANSION VESSEL: with a capacity of 10% of the total water content of the thermocooker and the
system. This must be positioned at the highest point of the system, at least 2m above the radiator placed at the
highest level.
2.
SAFETY PIPE : that connects by means of the shortest path without descending routes or siphoning the flow of
the thermo stove with the top part of the tank described in point 1. The safety pipe must have the minimum gas
section of 1''.
3.
LOAD PIPE : that connects the bottom of the tank of point1 with the system's return pipe.
It must have a minimum gas section of ¾''.
All these elements must not, for any reason, have intercepting objects inserted, as these could accidentally
exclude them, and they must be placed in an area not subject to freezing, seeing that, if they should freeze, the
boiler frame could break or even explode.
In case of exposure to ice, it is opportune to add a sufficient quantity of anti-freeze to the water in the system,
enough to completely eliminate the problem.
In no way should water circulate in the small tank in-between the safety pipe and load pipe, seeing as this
oxidises of the water and consequently this quickly corrodes the thermo stove and system body.
4.
HEAT DISCHARGE VALVE: permits an extra positive safety, capable of preventing boiling, even if there is no
electric power.
It consists of a valve, similar to a pressure safety valve, but differs, seeing that it opens once the pre-calibrated
temperature (normally 94-95° C) is reached. It disch arges hot water from the system flow pipe, and the water is
replaced with the same quantity of cold water, supplied from the tank vessel load pipe, this way reducing the
excessive heat.
5.
SAFETY VALVE FROM 1,5bar: maximum operation pressure allowed for the system is 1,5 bar (equal to 15m
of the water column). Higher pressures can cause deformation and breakage of the boiler body.
6.
SAFETY DEVICES envisioned by Regulations in vigour.
7.
CIRCULATION PUMP : preferably fitted on the return pipes to avoid diffusion of extremely high temperature
water, however ensure that it does not make water circulate in the open vessel tank as this would cause
continuous oxidation of water which would quickly corrode the boiler body.
It must also be connected electronically so that it will only work when the water temperature reaches 65-70° C. To
achieve this one can use the electronic control unit, available as an OPTIONAL with the thermo stove, or by
using a sleeve thermo switch fitted directly on the flow pipe and calibrated at 65-70° C.
8. AUTOMATIC THERMOSTATIC MIXING VALVE – (see chapter 3.3)
IMPORTANT: temperature safety sensors must be in place on the machine at a distance no greater than 30 cm from
the flow connection of the thermo-product.
Whenever the thermo products lack a device, those missing can be installed on the thermo product flow pipe, within a
distance no greater than 1m from the thermo product.
ATTENTION: For no reason must the fire be ignited before the system has been completely filled with water;
doing this would lead to serious damage of the entire structure. The system must be filled by
means of the loading pipe directly from the open vessel tank in a way to prevent an excessive water
pressure network deforming the body of the thermoheating stove.
The system must be kept constantly full of water even during the periods when the use of the thermoheating stove is
not requested. During the winter, inactivity must be faced with the addition of antifreeze.
3.2.

CLOSED expansion VESSEL system

It is COMPULSORY that the CLOSED expansion VESSEL system is provided with:
1. A 3 bar SAFETY VALVE:
water column). Higher pressures can cause deformation and breakage of the boiler body
2. AUTOMATIC THERMOSTATIC MIXING VALVE – (see chapter 3.3)
3. HEAT DISCHARGE VALVE or HEAT SAFETY DISCHARGE (positive safety, therefore, this continues
discharge, should the valve be damaged)
4. CLOSED EXPANSION VESSEL
5. PUMP CONTROL THERMOSTAT
6. NOISE ALARM ACTIVATION THERMOSTAT
7. NOISE ALARM
8. TEMPERATURE INDICATOR
24
maximum operation pressure allowed for the system is 3 bar (equal to 30m of the
Instructions for installation, use and maintenance – EN – Rev.01