System Layout 5 - Viessmann B2HB 45 Installation Instructions Manual

B2hb series vitodens 200-w wall-mounted, gas-fired condensing boiler
Table of Contents

Advertisement

Vitodens 200-W B2HB 45, 57 Installation

System Layout 5

Vitodens 200-W, B2HB with...
- DHW storage tank
- one heating circuit with mixing valve
- one heating circuit without mixing valve
- low-loss header
Legend
Vitodens 200-W B2HB boiler with
A
Vitotronic 200, HO1B outdoor reset control
B
Outdoor temperature sensor !
Vitotrol remote (optional)
C
D
Under floor heating circuit
E
Radiator heating circuit
Boiler circuit pump
F
20
G
Mixing valve temperature sensor ?
Kit for heating circuit with mixing valve
H
Domestic hot water storage tank
I
J
DHW tank temperature sensor %
Expansion tank
K
Temperature and pressure relief valve
L
M
Pressure relief valve
DHW recirculation pump
N
O
DHW circulating pump sA
P
Heating circuit pump
Low-loss header
Q
R
Viessmann temperature sensor for low-loss header ?
Heating circuit pump
S
*
Function based on coding of address 33
*
28/20
*
28/20
Installation of different heating circuits...
radiator heating circuit (high-temp. circuit)
under floor heating circuit with 3-way mixing valve
(low-temp. circuit)
DHW production
... with the following flow conditions:
The total flow rate of the two heating circuits is greater
than the maximum possible water flow rate of the
Vitodens 200-W B2HB boiler (see page 31 for maximum
water flow rate of boiler).
The use of a low-loss header is strongly recommended.
The low-loss header is available as accessory part.
The 3-way mixing valve, built-in to achieve the low-
temperature level of the under floor heating circuit, is
controlled by an accessory kit for a heating circuit with
mixing valve.
IMPORTANT
DHW circulating pump O must pump into the Vitodens
200-W B2HB boiler (as illustrated).
Boiler Connections
37