Gas Supply; Flue Installation - IDEAL LOGIC COMBI ESP1 24 Installation And Servicing

Hide thumbs Also See for LOGIC COMBI ESP1 24:
Table of Contents

Advertisement

1.8 GAS SUPPLY

The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an adequate
supply of gas. An existing service pipe must NOT be used without
prior consultation with the local gas supplier.
The boiler MUST be installed on a gas supply with a governed
meter only.
A gas meter can only be connected by the local gas supplier or
by a Gas Safe Registered Engineer. In IE by a Registered Gas
Installer (RGII).
An existing meter should be checked, preferably by the gas
supplier, to ensure that the meter is adequate to deal with the rate
of gas supply required.
It is the responsibility of the Gas Installer to size the gas installation
pipework in accordance with BS.6891. Whilst the principle of the
1:1 gas valve ensures the Logic range is able to deliver it is full
output at inlet pressures as low as 14mb, other gas appliances in
the property may not be as tolerant. When operating pressures
are found to be below the minimum meter outlet of 19mb these
should be checked to ensure this is adequate for correct and safe
operation.
Allowing for the acceptable pressure loss of 1mb across the
installation pipework, it can be assumed that a minimum permitted
operating pressure of 18mb will be delivered to the inlet of
the appliance. (Reference BS.6400-1 Clause 6.2 Pressure
Absorption).
The external gas cock could further reduce the operating pressure
when measured at its test point. The pressure drop is relative to
the heat input to the boiler (kW), refer to graph below.
Gas Cock Pressure Drop
3
2.5
2
1.5
1
0.5
0
0
10
IMPORTANT.
Ensure all gas valve connections are gas tight with a gas
soundness check up to the gas control valve.
Installation pipes must be fitted in accordance with BS.6891. In IE
refer to IS.813:2002.
The complete installation MUST be tested for gas tightness and purged
as described in the above code.

1.9 FLUE INSTALLATION

Pluming will occur at the terminal so terminal positions where this
could cause a nuisance should be avoided.
The flue must be installed in accordance with the recommendations
of BS.5440-1.
In IE refer to I.S. 813.
The following notes are intended for general guidance:
1. The boiler MUST be installed so that the terminal is exposed to
external air.
12
SECTION 1 - GENERAL
20
30
40
Heat Input to Boiler (kW)
2. It is important that the position of the terminal allows the free
passage of air across it at all times.
3. Minimum acceptable spacing from the terminal to obstructions
and ventilation openings are specified in
Table 4.
4. Where the lowest part of the terminal is fitted less than 2m
above a balcony, above ground or above a flat roof to which
people have access then the terminal MUST be protected by a
purpose designed guard.
Terminal guards are available from boiler suppliers. (Ask for
TFC flue guard model no. K6 - round, plastic coated). In case
of difficulty contact:
TFC Group.
Tower House, Vale Rise
Tonbridge. Kent TN9 1TB
Ensure that the guard is fitted centrally.
5. The flue assembly shall be so placed or shielded as to prevent
ignition or damage to any part of any building.
6. The air inlet/products outlet duct and the terminal of the boiler
MUST NOT be closer than 25mm to combustible material.
Detailed recommendations on the protection of combustible
material are given in BS.5440-1.
IMPORTANT. It is essential to ensure, in practice, that products
of combustion discharging from the terminal cannot re-enter the
building or buildings through any openings into the building such
as ventilators, windows, doors, or other sources of natural air
infiltration, such as forced ventilation openings etc.
If products of combustion re-entry is identified or suspected this
should be immediately investigated and corrected following the
guidance provided in the current Gas Industry Unsafe Situation
Procedure.
Table 4 - Balanced Flue Terminal Position
Flue Terminal Positions
1. Directly below, above or alongside an open
window, air vent or other ventilation opening.
2. Below guttering, drain pipes or soil pipes.
3. Below eaves.
4. Below balconies or a car port roof.
50
5. From vertical drain pipes or soil pipes.
6. From an internal or external corner or to a
boundary alongside the terminal.
7. Above adjacent ground, roof or balcony level.
8. From a surface or a boundary facing the terminal.
9. From a terminal facing a terminal.
10. From an opening in a car port
(e.g. door or window) into dwelling.
11. Vertically from a terminal on the same wall.
12. Horizontally from a terminal on the wall.
13. Above the roof pitch with roof slope of all angles.
Above flat roof.
14. From a single wall face.
From corner walls.
15. Below velux window
16. Above or side of velux window
* Only one reduction down to 25mm is allowable per installation
otherwise BS5440-1 dimensions must be followed.
Tel. + 44 (0) 01732 351 680
Fax. + 44 (0) 01732 354 445
www.tfc-group.co.uk
BS5440-1
BS5440-1
BS5440-1
BS5440-1
BS5440-1
Vertical Terminals
Installation and Servicing
Min. Spacing*
300mm
25mm*
75mm
25mm*
200mm
25mm*
200mm
25mm*
150mm
25mm*
300mm
300mm
600mm
1,200mm
1,200mm
1,500mm
300mm
300mm
300mm
300mm
300mm
2000mm
600mm

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Logic combi esp1 30Logic combi esp1 35

Table of Contents