SECTION 7 − OPERATING AUXILIARY EQUIPMENT

7-1. Generator Power Panel Receptacles

4
If unit does not have GFCI recep-
tacles, use GFCI-protected exten-
sion cord.
.
Generator power decreases as weld
current increases.
1
240 V AC Receptacle RC1
RC1 supplies 60 Hz single-phase power at
weld/power speed. Maximum output is 5
kVA/kW (peak) or 4.5 kVA/kW (continu-
ous).
2
120 V 20 A AC Duplex Receptacle
RC2
OM-228 042 Page 30
1
3
120 V 20 A AC Duplex Receptacle
RC3
RC2 and RC3 supply 60 Hz single-phase
power at weld/power speed. Maximum
output from RC2 or RC3 is 2.4 kVA/kW.
NOTICE − Do not parallel the two 120 VAC
duplex receptacles.
4
Supplementary Protector CB1
CB1 protects the receptacles from over-
load. If CB1 opens, the receptacles do not
work. Move switch to the On position to re-
set.
.
Complete Parts List available at www. MillerWelds.com
2
3
.
If supplementary protector continues
to open, contact Factory Authorized
Service Agent.
Combined output of all receptacles limited
to 4.5 kVA/kW continuous rating of the
generator (See Section 13 − Generator
Power Guidelines).
EXAMPLE: If 10 A is drawn from each 120
volt duplex receptacle, only 8 A is available
from the 240 V receptacle.
2 x (120 V x 10 A) + (240 V x 8 A) = 4.5 kVA/
KW.
229 573-A