Grounding When Supplying Building Systems - Miller Electric Big Blue 402D Owner's Manual

Miller electric owner's manual welding engine driven welding generator big blue 402d, big blue 502d, big blue 602dr
Table of Contents

Advertisement

14-3. Grounding When Supplying Building Systems

2
14-4. How Much Power Does Equipment Require?
1
EXAMPLE 1: If a drill uses 4.5 amperes at 115 volts, calculate its running power
requirement in watts.
EXAMPLE 2: If three 200 watt flood lamps are used with the drill from Example 1,
add the individual loads to calculate total load.
The total load applied by the three flood lamps and drill is 1120 watts.
OM-495 Page 84
1
GND/PE
3
3
2
3
AMPERES x VOLTS = WATTS
4.5 A x 115 V = 520 W
The load applied by the drill is 520 watts.
(200 W + 200 W + 200 W) + 520 W = 1120 W
Return To Table Of Contents
2
Use ground device as stated
in electrical codes.
VOLTS 115
AMPS
4.5
Hz
60
1
Equipment Grounding
Terminal
2
Grounding Cable
Use #10 AWG or larger insulated
copper wire.
3
Ground Device
Y Ground generator to system
earth ground if supplying
power to a premises (home,
shop, farm) wiring system.
ST-800 576-B
1
Resistive Load
A light bulb is a resistive load and
requires a constant amount of power.
2
Non-Resistive Load
Equipment with a motor is a non-re-
sistive load and requires approxi-
mately six times more power while
starting the motor than when running
(see Section 14-8).
3
Rating Data
Rating shows volts and amperes, or
watts required to run equipment.
S-0623

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Big blue 502dBig blue 602dr

Table of Contents