8-4. Generator Power Receptacles (CE Models)

4
.
Generator power is not affected by weld
output.
1
130 V 32 A AC Receptacle RC1
2
220 Volt 16 A AC Receptacle RC2
3
130 Volt 16 A AC Receptacle RC3
Receptacles supply 60 Hz single-phase
power at weld/power speed.
4
Circuit Breaker CB1
5
Circuit Breakers CB2 And CB3
CB1 protects RC1 and the generator wind-
1
ing from overload. If CB1 opens, RC1 and
RC2 do not work. Place switch in On position
to reset breaker.
CB2 protects RC2, and CB3 protects RC3
from overload. If a circuit breaker opens, the
receptacle does not work. Place switch in On
position to reset breaker.
.
If a circuit breaker continues to open,
contact Factory Authorized Service
Agent.
Return To Table Of Contents
2
5
Maximum output is 4 kVA/kW from RC1 and
2.2 kVA/kW from RC2 or RC3. Maximum
output from all receptacles is 4 kVA/kW.
Combined output of receptacles is limited to
4 kVA/kW output of generator. If maximum
output is exceeded, auxiliary equipment will
stop or not run properly.
EXAMPLE: If 20 A is drawn from RC1, only
8 A is available at each of the other
receptacles.
(110 V x 20 A) + ( 110 V x 8 A) + (110 V x 8
A) = 4 kVA/kW.
3
Ref. 204 258
OM-495 Page 45