Advertisement

Table 5a. Esprit Models 3 and 4 Rack UPS Specifications (Continued)
Item
Design standards
Input connection
Output connections
Auxiliary DC input
Size
Weight
MTBF

Sizing Guide and Battery Runtimes

Unix Server
PC Server
1
server
VA
500
Esprit 3 SLR
90
Esprit 3 SLR
+ 1 Ext. Batt.
240
Esprit 3 SLR
+ 2 Ext. Batt.
360
Esprit 4 SLR
120
Esprit 4 SLR
+ 1 Ext. Batt.
240
Esprit 4 SLR
+ 2 Ext. Batt.
360

Extended Battery Runtime

Extended Batteries (Qty.)
Model
Esprit 3
Esprit 4
Note: All battery times above are typical.
5—2
Specification
Safety; UL, cUL 1778, Emissions;
FCC A, Surge protection; ANSI
C62.41, Transportation; (drop test),
IEC 68 level 1, (vibration), IEC
68.2-6 level 3, testing; PowerCet
tested
NEMA 5-30/50 w/ six foot cord
1 NEMA 5 30/50 and 4 5-15
1 each special female connector on
UPS (18" cord and male connector
on optional battery)
1 each (UPS, battery)
65/70 lbs.. total
200K hours
1
server
2
3
servers
servers
1000
1500
40
28
90
40
150
90
50
30
100
72
180
110
(internal plus extended battery, in minutes, 0.7 PF)
1
2
12
30
15
25
Comment
Provides additional battery time
5.25" X 7.25" X 19"
(In minutes, 0.62 PF)
2
servers
4
5
servers
servers
2000
2500
19
11
28
19
60
45
20
15
45
35
75
55
3
4
45
60
38
49
3
servers
6
7
servers
servers
3000
3500
6
15
38
12
9
28
24
45
35
4
servers
8
servers
4000
7
18
29

Advertisement

loading

This manual is also suitable for: