Performance & Product Specifications

Run Time Chart for Various Loads

25% Load
Model
300
50
500
35
650
45
800
35
1200
35

Product Specifications

300 / 500
UPS VA rating:
300 / 480
(2.3 / 4 A)
UPS W rating:
180 / 285
Surge suppressor
900 / 720
VA rating:
(7.5 A / 6 A)
Input/Output voltage:
106/120/127 VAC*
50/60 Hz
Deep discharge
4 hrs. max
protection:
run time
UPS back-up time:
6/4 minutes
UPS output
Modified sine
wave shape:
Load shedding
receptacles:
Surge suppressor
185
joule rating:
Input cord:
6 foot with rotating
NEMA 5-15 plug
Circuit breaker:
10 amp
Agency approvals:
UL, cUL, FCC
Recharge time:
8 hours
Battery:
1 each 12 volt, 5 Ah
Battery life:
3 years
UPS current limit:
>100% Load
Operating temperature:
0-35 C/32-96 F
Storage temperature:
0-50 C/32-122 F
Size:
10" X 10" X 3.2"
Weight:
9 lbs.
Warranty:
2 years
parts and labor
Accessories:
6' fax/modem cable,
communication cable
(RS232 or USB)
* Input voltage and transfer voltage to battery is user selectable. Go to UPS Manager/UPS Driver in
Solution Pac software to adjust.
page 6
86-153506-00 Rev. A01
50% Load
75% Load
19
12
15
8
19
12
16
8
15
8
650 / 800
1200
650 / 800
1200 (10 A)
(5.7 / 6.7 A)
(10 A)
420 / 520
780
550 / 400
(4.6 A / 3.3 A)
106/120/127 VAC*
106/120/127 VAC*
50/60 Hz
50/60 Hz
4 hrs. max
4 hrs. max
run time
run time
7/4 minutes
4 minutes
Modified sine
Modified sine
3 grouped
185
185
6 foot with rotating
6 foot with rotating
NEMA 5-15 plug
NEMA 5-15 plug
10 amp
10 amp
UL, cUL, FCC
UL, cUL, FCC
8 hours
8 hours
2 each 12 volt, 5 Ah
3 each 12 volt, 5 Ah
3 years
3 years
>100% Load
>100% Load
0-35 C/32-96 F
0-35 C/32-96 F
0-50 C/32-122 F
0-50 C/32-122 F
12" X 12" X 3.2"
14" X 14" X 3.2"
13 lbs.
18 lbs.
2 years
2 years
parts and labor
parts and labor
6' fax/modem cable,
6' fax/modem cable,
communication cable
communication cable
(RS232 or USB)
(RS232 or USB)

Troubleshooting

Condition
LED "
" (green) is off,
100% Load
UPS has no output
UPS has little or no back-up time
6
4
7
LED "
" flashes (green)
4
audible alarm beeps often
4
(UPS transfers to battery)
LED "
" (red), beeping
!
audible alarm
LED "
" (green),
1 beep every 10 seconds
LED "
" (green),
1 beep every 3 seconds
LED "
with beeping audible alarm
LED "
" (green) and
LED "
!
" (red)
MGE maintains a toll-free number for technical support for US and Canadian customers. Call for
assistance as shown in the "Service and Parts" section of this manual or visit our web site at:
www.mgeups.com

Model Identification

Ellipse
Model
300 VA
300 VA
500 VA
500 VA
500 VA
650 VA
800 VA
1200 VA
MGE UPS Systems
MGE UPS Systems
Item(s) to Check
Check that UPS is plugged in, AC power is
"on" to UPS and UPS is turned "on".
Charge UPS overnight and retry. After 3-5
years, consider replacing batteries if back-up
time is short (MGE P/N 3088201000).
Many low voltage events or poor voltage and
regulation at receptacle. Try another
receptacle.
Potential internal failure. Restart UPS. Call for
assistance If red LED reappears.
UPS operation on battery due to utility
power failure
UPS operation on battery
and battery near exhaustion
" (red),
UPS lightly or heavily overloaded.
Reset circuit breaker on UPS if necessary.
Reduce load and restart UPS
Faulty battery. Recharge battery.
Replace battery if fault reappears.
Communications
Fax,
Modem/Network
Protection
USB
Fax Modem
USB
RS232
Fax Modem
RS232
USB
RS232
Ellipse User's Manual
MGE Part
UPC Codes
Number
89301
635760893014
89303
635760893038
89304
635760893045
89305
635760893052
89306
635760893069
89308
635760893083
89310
635760893106
89314
635760893144
MGE GREEN SWEEP
Call MGE to return your UPS for free
recycling to a US EPA-certified recycling
US
center and help protect our environment.
page 7