Viessmann VITOMAX 200-HS Operating And Service Instructions page 38

Oil/gas high pressure steam boiler with or without economiser rated steam output 0.5 to 4.0 t/h
Hide thumbs Also See for VITOMAX 200-HS:
Table of Contents

Advertisement

Commissioning
Commissioning
Verification
Create a first commissioning report
where the established and set values are
recorded. This report must be signed by
the customer.
Instructions
Instruct the operating personnel after the
first commissioning. Create a report
regarding these instructions.
Returning the boiler into use after idle periods
Generally, it would be the local operators
who would return the boiler into use after
an idle period. Starting the boiler from
the external control room is not permis-
sible.
The boiler must be returned into use in
the following sequence:
■ Walk around the system to visually
check its correct condition
■ Control panel commissioning – Circuit
breaker ON
■ Commissioning the feed
■ Checking the water level and the func-
tion of the water level indicator as well
as that of the water level control
■ Commissioning the combustion with a
closed steam valve
Shutdown
Shutdown means shutting down the sys-
tem via the circuit breaker at the control
panel.
38
(cont.)
■ Controlling the output to partial load or
stage 1
■ Check the water level and, upon
reaching high water, reduce the water
level by means of a blow-down.
■ When the boiler pressure has risen to
3 bar below the permissible operating
pressure, slowly open the steam
valve.
■ Further checks as described in chap-
ter "Utilisation and operation".
■ For one hour after starting the boiler
the system should be supervised by an
operator (only applicable to systems
without temporary supervision).