SERVICING
S-16C CHECKING ECM MOTOR WINDINGS
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Disconnect the 5-pin and the 16-pin connectors from the
ECM power head.
2. Remove the 2 screws securing the ECM power head and
separate it from the motor.
3. Disconnect the 3-pin motor connector from the power
head and lay it aside.
4. Using an ohmmeter, check the motor windings for con-
tinuity to ground (pins to motor shell). If the ohmmeter
indicates continuity to ground, the motor is defective and
must be replaced.
5. Using an ohmmeter, check the windings for continuity
(pin to pin). If no continuity is indicated, the thermal limit
(over load) device may be open. Allow motor to cool and
retest.
3-pin motor
connector
16-pin
connector
5-pin
connector
S-16D ECM CFM ADJUSTMENTS MBE / AEPF
MBE MOTOR
This section references the operation characteristics of the
MBE/AEPF models motor only. The ECM control board is
factory set with the dipswitch #4 in the "ON" position and all
other dipswitches are factory set in the "OFF" position. When
MBE/AEPF are used with 2-stage cooling units, dipswitch
#4 should be in the "OFF" position.
For most applications, the settings are to be changed
according to the electric heat size and the outdoor unit
selection.
The MBE/AEPF products use a General Electric ECM
motor. This motor provides many features not available on
the traditional PSC motor. These features include:
Improved Efficiency
Constant CFM
Soft Start and Stop
Improved Humidity Control
36
MOTOR SPEED ADJUSTMENT
Each ECM™ blower motor has been preprogrammed for
operation at 4 distinct airflow levels when operating in Cool-
ing/Heat Pump mode or Electric Heat mode. These 4 distinct
levels may also be adjusted slightly lower or higher if desired.
The adjustment between levels and the trim adjustments are
made by changing the dipswitch(s) either to an "OFF" or "ON"
position.
DIPSWITCH FUNCTIONS
The MBE / AEPF air handler motors have an electronic
control that contains an eight (8) position dip switch. The
function of these dipswitches are shown in Table 1.
Dipsw itch Num ber
1
2
3
4
5
6
7
8
CFM DELIVERY
Tables 2, 3, 5 and 6 show the CFM output for dipswitch
combinations 1-2, and 5-6.
Electric Heat Operation
Model
MBE1200
MBE1600
MBE2000
Cooling/Heat Pump Operation
Model
Switch 5
MBE1200
MBE1600
TM
MBE2000
Function
Electric Heat
N/A
Indoor Therm ostat
Cooling & Heat Pum p CFM
CFM Trim Adjust
Table 1
Switch 1
Switch 2
CFM
OFF
1,200
OFF
ON
1,000
OFF
800
OFF
ON
ON
600
ON
1,600
OFF
OFF
1,400
ON
OFF
OFF
1,200
ON
ON
ON
1,000
OFF
2,000
OFF
ON
OFF
1,800
OFF
1,600
ON
ON
ON
1,200
Table 2
Switch 6
CFM
1,200
OFF
OFF
ON
1,000
OFF
OFF
800
ON
ON
ON
600
OFF
1,600
OFF
1,400
ON
OFF
1,200
OFF
ON
ON
1,000
ON
2,000
OFF
OFF
ON
1,800
OFF
OFF
1,600
ON
ON
ON
1,200
Table 3