Table 1 – Installation overview
Refer to the installation mechanical and electrical sections of this manual for detailed installation instructions.
Requirement
Trane supplied
Trane installed
Rigging
Isolation
Electrical
Disconnect switch (optional)
Water piping
Pressure relief
Relief valves
Insulation
Insulation (optional)
Table 2 - General data
207
Evaporator type
EG 120
Condenser type
CG 120
Compressor type
K1/K1
Oil charge (l)
6/6
Oil type
Refrigerant charge
(kg)
39/39
Operating weight
(kg)
2620
Shipping weight
(kg)
2450
Length (mm)
2880
Width (mm) (1)
890
Height (mm) (1)
1789
(1) With compressor sound enclosure and disconnect switch handle not mounted.
8
General
Information
Trane supplied
Field installed
Isolation pads
Flow switches (may be field supplied)
Flow switches (may be field supplied)
208
210
211
EG 120
EG 140
EG 170
CG 120
CG140
CG 170
K2/K2
L1/L1
L2/L1
6/6
7/7
7/7
39/39
60/60
60/60
2620
3370
3450
2450
3050
3150
2880
4150
4150
890
890
890
1789
1832
1832
212
214
216
EG 170
EG 200
EG 200
CG 170
CG 200
CG 200
L2/L2
M1/M1
M2/M1
7/7
8/8
8/8
OIL 023 E or OIL 048 E
60/60
60/60
60/60
3450
3725
3725
3150
3500
3500
4150
4150
4150
890
890
890
1832
1832
1832
Field supplied
Field installed
Safety chains
Clevis connectors
Lifting beam
Isolation pads
Disconnect switch
BAS wiring (optional)
Water pump contactor
Thermometers
Water flow pressure gauges
Isolation and balancing valves water piping
Vents and drain valves
Pressure relief valves
Vent line
Insulation
217
218
220
EG 200
EG 250
EG 250
CG 200
CG 230
CG 230
M2/M2
N1/M2
N1/N1
8/8
8/8
8/8
60/60
69/69
69/69
3725
4325
4500
3500
3900
4050
4150
4150
4150
890
890
890
1832
1932
1932
222
224
EG 340
EG 340
CG 230 CG 230
N2/N1
N2/N2
11/8
11/11
74/74
74/74
4925
5000
4250
4400
4150
4150
890
890
2041
2041
RTWB-SVN01B-E4