Electrical Parts ....................................................................................................................................... 9
Microcomputer Control System .....................................................................................................11
Page 1
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE SERVICE MANUAL S7222AYAP24CE SPLIT SYSTEM ROOM AIR CONDITIONERS INDOOR UNIT AH-AP18CE AY-AP18CE AH-AP24CE AY-AP24CE MODELS OUTDOOR UNIT AU-A18CE AE-A18CE AU-A24CE AE-A24CE In the interests of user-safety (Required by safety regulations in some countries) the set should be restored to its original condition and only parts identical to those specified should be used.
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE SPECIFICATIONS ITEMS INDOOR UNIT OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT AY-AP18CE AE-A18CE AY-AP24CE AE-A24CE Cooling capacity Heating capacity Moisture removal Liters/h Electrical data Phase – Single Rated frequency Rated voltage 220 – 240 Rated current Cool 9.3 –...
Page 3
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE ITEMS INDOOR UNIT OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT AH-AP18CE AU-A18CE AH-AP24CE AU-A24CE Cooling capacity Moisture removal Liters/h Electrical data Phase – Single Rated frequency Rated voltage 220 – 240 Rated current 9.3 –...
Page 15
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE TO TERMINAL BOARD TO TERMINAL BOARD BOTTOM“N” TOP“N” FROM TERMINAL BOARD BOTTOM “1”“BROWN” FROM CLEANING SWITCH 2 TO TERMINAL BOARD TOP “3” TO TERMINAL BOARD TOP “2” FROM CLUSTER GENERATOR FROM FAN MOTOR...
Page 16
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE TO TERMINAL BOARD TO TERMINAL BOARD BOTTOM“N” TOP“N” TO TERMINAL BOARD BOTTOM “1” FROM CLEANING SWITCH 2 TO TERMINAL BOARD TOP “4” TO TERMINAL BOARD TOP “3” TO TERMINAL BOARD TOP “2” FROM CLUSTER GENERATOR FROM...
Page 17
CLUSTER GENERATOR FROM FAN MOTOR FB441 FB441 FB441 FB441 TO TERMINAL BOARD TOP“N” BCN101(BCN201) FROM TERMINAL BOARD TOP“1”“BLACK” FROM FAN MOTOR FROM THERMISTOR FROM CLUSTER GENERATOR FROM CLEANING SWITCH 1 FROM LOUVER MOTOR Figure L-7. Printed Wiring Diagram for AH-AP18CE...
Page 18
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE TO TERMINAL BOARD TO TERMINAL BOARD BOTTOM“N” TOP“N” TO TERMINAL BOARD BOTTOM “1” FROM CLEANING SWITCH 2 TO TERMINAL BOARD TOP “2” FROM CLUSTER GENERATOR FROM FAN MOTOR FB441 FB441 FB441 FB441 TO TERMINAL BOARD TOP“N”...
AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE FUNCTIONS HEAT operation AH-AP18CE/AP24CE are noty provided with the In the “HEAT” mode, the thermostat circuit is heating function controlled by six thermostat lines (H01 thru H4). Temperature control characteristic 37.0 COOL operation 36.0 In the “COOL”...
Page 20
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE DRY operation Table Y-1 On the switch on, the compressor always starts to Compressor Fan speed operate for 2 minutes with fan speed "DL" . The microcomputer reads the room temperature 2 Cooling zone "DH"...
Page 21
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE Hot-Keep Overheating protection system This function automatically controls the on-off When overloading occurs during the heating operation, operation of the indoor fan motor in accordance this system controls the outdoor fan motor according to...
Page 22
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE Current control Defrost start 60sec. 60sec. This system, in order to prevent overcurrent Compressor during heating operation, controls the outdoor fan motor and changes the indoor fan motor speed by MAX. 7min. detecting total current. When the current exceeds Reverse Valve P2, the outdoor fan motor is automatically turned...
Page 23
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE Automatic air conditioning Outputs in each operation mode automatic air conditioning is selected, the operation mode and preset temperature are set Table Y-5 automatically according to the room temperature on starting operation.
Page 26
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE Diagnosis procedure When indoor fan motor is out of order or compressor lock occurs, the compressor, indoor fan motor, outdoor fan motor, and louver are all stopped and the operation LED(red) turns on or off synchronously with the timimg of the timer LED.
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE TROUBLESHOOTING GUIDE OF CONTROL CIRCUIT The machine does not function at all with remote controller and switch on the indoor unit. Check the cleaning switch 2(1),CN9 CN8, and lead wires. Replace the cleaning switch 2(1).
Page 28
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE The machine does not function with remote controller Push button "O/I" on the wireless remote controller. Is transmitting Are batteries of the indicator of the remote wireless remote controller controller active ? proper ? Replace the batteries with new ones.
Page 29
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE For AY-AP18CE/AE-A18CE, AH-AP18CE/AU-A18CE The room is not cooled at all or not cooled. The compressor does not operate. Fig. 1 Temperature properties of indoor thermistors Room temperature Heat exchange thermistor TH1 thermistor TH2...
Page 30
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE For AY-AP24CE/AE-A24CE, AH-AP24CE/AU-A24CE The room is not cooled at all or not cooled. The compressor does not operate. Push the button "AUX." on the indoor unit, for more than 5 sec. Using a tester, measure voltage at the terminals on the terminal board.
Page 31
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE For AY-AP24CE/AE-A24CE, AY-AP18CE/AE-A18CE The room is not heated at all or not heated. The compressor does not operate. Select HEAT MODE with remote controller. And then start operation. Push the button of "AUX" on the indoor unit, for more than 5 sec.
AE-A24CE AU-A18CE AU-A24CE DISASSEMBLING PROCEDURE FOR INDOOR UNIT MODEL(AH-AP18CE/AP24CE,AY-AP18CE/AP24CE) CAUTION:DISCONNECT THE UNIT FROM THE POWER SUPPLY BEFORE ANY SERVICING Open the Opne panel, remove 2 Air Filters. Remove 6 screws fixing the Front panel. Open the Louver frame.unlook the hooks,and pull Remove the screw fixing the Cord holder.
Page 38
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE Close the Open panel. pushing the nail of the Remove a screw fixing the Control box cover. Front panel, and lift the Front panel up. Cut the fixing band and Remove the Cover B. Remove the unit-to-unit wiring from the Terminal board.
Page 39
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE Remove the Thermistor of the Evaporator. Cut the fixing band and Remove the Holder. Remove 2 screws fixing the Control box and Remove Connectors. remove it.
Page 40
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE Remove the Evaporator from the Cabinet. Remove a screw fixing the drain pan and pull Drain pan toward you. Remove 4 screws fixing the Side cover R, and pull up the Cross flow fan. Remove the Drain cover from the Evaporator.
Page 41
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE The Electric Control box. Remove a screw fixing the Cord holder and 2 screws fixing the Terminal board. Remove the screw fixing the Receiving filter. Remove 2 screws fixing the Transformer and pull Remove the 2 Switch and Photo detector unit.
Page 42
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE The LOUVER FRAME UNIT and related The DRAIN PAN and related Remove the screw fixing the FRAME GUIDE on Remove the screw fixing the Drain pan on both both side and take off the LOUVER UNIT. side.
Page 43
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE How to remove the Hi Voltage UNIT. Remove the connector of Louver motor and take off the Wire and Holder. Remove 2 screws fixing Holder. Push the one of the Vertical louver.
AY-AP18CE AY-AP24CE AH-AP18CEAH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE FOR OUTDOOR UNIT MODEL AE-A18CE/AE-A24CE DISASSEMBLING PROCEDURE OF THE CONTROL BOX Loose 1 screw fixing the cabinet (rear side). Loose 3 screws fixing the control cover. Loose 1 screw fixing the side cover. Loose 3 screw fixing the cabinet (right side).
Page 45
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE Loose 1 screw fixing the rear cabinet (left side). Remove 3 terminals. Loose 3 screws fixing the bulkhead. Cut nylon band. DISASSEMBLING PROCEDURE OF THE FAN Loose the fan nut and fan can take out.
Page 46
CKITTA002JBKZ High voltage unit (Plasma cluster unit) 2- 8 LHLD-A537JBFA LED holder 2- 9 LHLD-A542JBFA Holder 2-10 DPWBFA251JBKZ Control board unit [AH-AP18CE] 2-10 DPWBFA250JBKZ Control board unit [AH-AP24CE] 2-10 DPWBFA242JBKZ Control board unit [AY-AP18CE] 2-10 DPWBFA249JBKZ Control board unit [AY-AP24CE]...
Page 47
3- 5 PVLV-A223JBEZ Flare union (3/8") 3- 5 PVLV-A238JBEZ Flare union (1/2") [AH-AP24CE, AY-AP24CE] 3- 6 DEVA-A161JBKZ Evaporator sub assembly [AH-AP18CE, AY-AP18CE] 3- 6 DEVA-A165JBKZ Evaporator sub assembly [AH-AP24CE, AY-AP24CE] ACCESSORY PARTS 4- 1 CRMC-A561JBEZ Remote control [AH-AP18CE, AY-AP24CE] 4- 1...
Page 49
AY-AP18CE AY-AP24CE AH-AP18CE AH-AP24CE AE-A18CE AE-A24CE AU-A18CE AU-A24CE REF. NO. PART NO. DESCRIPTION Q'TY CODE CABINET AND UNIT PARTS 1- 1 LSUB-A024JBPZ Motor angle sub [AU-A18CE] 1- 2 CMOTLB002JBEZ Fan motor [AU-A18CE] 1- 2 CMOTLB015JBEZ Fan motor [AU-A24CE] 1- 3...