PC4000 MAIN BOARD
SPECIFICATIONS
Control Panel
16 zones
16 fully programmable supervised zones (EOL
resistor)
Audible alarm output
Bell output
700 mA, fused at 5 Amps, 12 VDC unregulated
Steady or pulsed output
Non-volatile RAM (Internal Memory)
Does not lose codes or system status on complete AC
and battery failure
Programmable output
Transistor switch sinks 3A to ground
Operation controllable through program options
Powerful 1.5 amp regulated power supply
500 mA auxiliary supply, 12 VDC unregulated
Separately fused for battery, auxiliary supply and bell
output
Electronic shut down protection of the COMBUS
Supervision for loss of AC power, low battery,
electronic shut down of modules
Internal clock locked to AC power frequency
Switched Auxiliary Supply Output
Programmable for several options
Battery
12 volt 4 Ah minimum rechargeable gel-cell or sealed
lead-acid battery
Transformer
16.5 VAC, 40VA
Values shown are in conformance with UL specifications which do not take into
account current that may be available from a stand-by battery.
Output Voltage
Typically, with normal AC on and a fully charged battery,
the output voltage will be 13.8 VDC. With AC off and the
battery discharging, the voltage will go below 10 volts
and then battery cutoff will occur preventing further
discharge. Devices that require power from the control
panel should be capable of operation over the voltage
range of 10 to 14 VDC.
Remote Keypad
Four wire (QUAD) hook-up
Alphanumeric liquid crystal display
Built-in piezoelectric buzzer
Full annunciation of zones and system status
Dimensions 5.5" x 4.5" x 1" deep (150 x 114 x 25 mm)
Maximum current draw of 55 mA