Cooling Capacities For Wj240 - York WJ 180 Technical Manual

Single package gas/electric units and single package air conditioners
Hide thumbs Also See for WJ 180:
Table of Contents

Advertisement

262291-YTG-F-1009
TABLE 5: COOLING CAPACITIES FOR WJ240
Air on Evaporator Coil
Total
WB
CFM
Cap.
(°F)
(MBH)
77
287
72
263
5000
67
238
62
219
77
304
72
278
6000
67
252
62
232
57
229
77
320
72
293
7000
67
265
62
244
57
241
77
337
72
308
8000
67
279
62
257
57
254
72
302
67
274
8500
62
252
57
249
72
296
67
268
9000
62
247
57
244
77
270
72
246
5000
67
222
62
206
77
285
72
259
6000
67
234
62
217
57
216
77
299
72
273
7000
67
247
62
228
57
227
77
314
72
286
8000
67
259
62
239
57
238
72
280
67
253
8500
62
234
57
233
72
274
67
248
9000
62
229
57
228
1.
The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
12
75°F
2
Sensible Capacity (MBH)
Total
1
Return Dry Bulb (°F)
Input
(kW)
90
85
80
15.1
117
99
80
14.6
152
134
115
14.2
187
168
150
13.8
215
198
176
15.2
133
111
89
14.8
171
150
128
14.3
210
188
166
14.0
228
217
195
13.8
229
227
205
15.4
149
123
98
14.9
190
165
140
14.4
233
207
182
14.1
241
235
214
13.9
241
240
225
15.5
165
135
107
15.1
210
181
153
14.6
254
227
199
14.2
254
254
233
14.1
254
254
245
15.0
213
184
155
14.5
249
230
202
14.2
249
249
239
14.0
249
249
245
14.9
216
187
157
14.4
244
224
205
14.1
244
244
244
13.9
244
244
244
95°F
17.6
105
93
73
17.3
147
127
108
17.0
188
162
143
16.7
205
197
169
17.8
127
104
82
17.5
166
143
120
17.2
204
181
159
16.8
216
210
188
16.6
216
216
193
17.9
149
116
90
17.6
184
158
132
17.3
220
201
175
17.0
227
224
207
16.7
227
227
212
18.1
171
128
98
17.8
203
174
145
17.5
236
220
191
17.1
238
238
226
16.9
238
238
232
17.7
206
177
147
17.4
232
224
194
17.1
233
233
227
16.8
233
233
230
17.7
209
179
150
17.4
227
227
197
17.1
228
228
228
16.8
228
228
228
Temperature of Air on Condenser Coil
*
Total
Total
1
Cap.
Input
(MBH)
(kW)
75
70
65
62
43
25
278
16.4
96
78
59
254
16.0
131
113
94
230
15.6
157
139
120
212
15.3
67
45
23
294
16.5
106
84
62
269
16.1
144
122
100
243
15.7
173
151
129
224
15.4
183
161
139
222
15.2
73
47
22
310
16.7
115
90
64
283
16.3
157
132
107
256
15.9
189
164
138
236
15.5
200
175
149
234
15.3
78
50
21
325
16.8
124
96
67
297
16.4
170
142
113
269
16.0
205
176
148
248
15.7
217
188
160
246
15.5
126
97
69
291
16.4
173
144
115
264
16.0
210
181
152
243
15.6
216
187
158
241
15.4
128
99
70
285
16.3
176
147
118
258
15.9
215
186
157
238
15.6
215
186
157
236
15.3
54
35
15
255
19.4
89
69
50
234
19.1
123
104
84
212
18.8
149
130
111
195
18.5
59
36
14
269
19.6
97
75
52
246
19.3
136
113
91
224
19.0
165
142
120
206
18.7
170
147
125
205
18.1
64
38
12
283
19.8
106
80
54
259
19.5
149
123
97
236
19.2
181
155
129
217
18.8
186
160
134
216
18.3
69
40
10
297
19.9
115
86
56
272
19.6
162
132
103
248
19.3
196
167
138
228
19.0
203
173
144
226
18.4
117
88
58
266
19.6
165
135
105
242
19.3
197
168
138
223
18.9
200
171
141
222
18.4
120
90
60
261
19.5
168
138
108
237
19.2
198
168
139
218
18.9
198
169
139
217
18.3
85°F
2
Sensible Capacity (MBH)
Return Dry Bulb (°F)
90
85
80
75
112
96
77
58
150
131
112
93
187
165
146
127
210
198
172
153
130
108
85
63
169
146
124
102
207
185
162
140
222
214
191
169
222
221
199
177
148
120
94
68
187
162
136
111
226
204
179
153
234
230
210
185
234
234
219
193
167
131
102
74
206
178
149
120
246
224
195
166
246
246
230
201
246
246
239
210
209
180
151
122
241
227
198
169
241
241
233
204
241
241
237
208
212
183
153
124
236
231
201
172
236
236
236
207
236
236
236
207
105°F
103
89
70
50
143
124
104
85
183
158
139
119
192
190
164
144
127
101
78
55
162
139
116
93
197
177
155
132
204
202
183
160
205
205
185
162
150
112
86
59
180
154
128
102
211
197
170
144
216
214
201
175
216
216
204
178
173
123
94
64
199
169
140
110
225
216
186
157
226
226
220
190
226
226
223
193
202
172
143
113
220
212
190
160
222
222
218
188
222
222
220
190
206
175
145
115
216
209
193
163
217
217
217
186
217
217
217
187
Johnson Controls Unitary Products
*
70
65
39
20
74
55
108
89
134
115
41
19
79
57
118
95
147
124
154
132
43
17
85
59
127
102
159
134
167
142
45
16
91
62
137
108
172
143
181
152
93
64
140
110
174
145
179
150
95
65
142
113
177
148
177
148
31
11
65
46
100
80
125
105
32
9
70
48
109
86
137
114
139
117
33
7
76
49
118
92
149
123
152
125
34
5
81
51
127
97
161
131
164
134
83
53
130
100
159
129
160
130
85
55
133
103
156
126
157
126

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wj 300Wj 240

Table of Contents