Wj Electrical Data W/Powered Convenience Outlet - High Static Drive - York WJ 180 Technical Manual

Single package gas/electric units and single package air conditioners
Hide thumbs Also See for WJ 180:
Table of Contents

Advertisement

262291-YTG-F-1009
TABLE 27: WJ ELECTRICAL DATA W/POWERED CONVENIENCE OUTLET - HIGH STATIC DRIVE MOTOR
COMPRESSORS
MODEL
(TON-
VOLTAGE
RLA
NAGE)
EACH
208
22.4
230
22.4
180
(15)
460
10.9
575
208
30.1
230
30.1
240
(20)
460
15.5
575
12.1
NOTE 1: HACR Type per NEC.
38
OD FAN
MOTORS
LRA
FLA EACH
EACH
164
2.1
164
2.1
100
1.2
8.3
78
0.9
225
2.4
225
2.4
114
0.9
80
0.6
ID
CONV
BLOWER
OUTLET
MOTOR
MODEL
AMPS
FLA
None
E18
20.0
10.0
E36
E54
E72
None
E18
20.0
10.0
E36
E54
E72
None
E18
10.0
5.0
E36
E54
E72
None
E18
7.5
4.0
E36
E54
E72
None
E18
24.2
10.0
E36
E54
E72
None
E18
24.2
10.0
E36
E54
E72
None
E18
12.1
5.0
E36
E54
E72
None
E18
10.3
4.0
E36
E54
E72
HEATER OPTION
AMPACITY
KW
STAGES
AMPS
0.0
~
~
13.5
1
37.5
27.0
2
74.9
40.6
2
112.7
54.1
2
150.2
0.0
~
~
18.0
1
43.3
36.0
2
86.6
54.0
2
129.9
72.0
2
173.2
0.0
~
~
18.0
1
21.7
36.0
2
43.3
54.0
2
65.0
72.0
2
86.6
0.0
~
~
18.0
1
17.3
36.0
2
34.6
54.0
2
52.0
72.0
2
69.3
0.0
~
~
13.5
1
37.5
27.0
2
74.9
40.6
2
112.7
54.1
2
150.2
0.0
~
~
18.0
1
43.3
36.0
2
86.6
54.0
2
129.9
72.0
2
173.2
0.0
~
~
18.0
1
21.7
36.0
2
43.3
54.0
2
65.0
72.0
2
86.6
0.0
~
~
18.0
1
17.3
36.0
2
34.6
54.0
2
52.0
72.0
2
69.3
Johnson Controls Unitary Products
MAX.
MIN.
FUSE/
CIRCUIT
1
BRKR
SIZE
(AMPS)
(AMPS)
88.8
110
88.8
110
131.2
150
178.4
200
187.7
200
88.8
110
91.6
110
145.8
150
167.4
175
210.7
225
44.3
50
45.8
50
72.9
80
83.7
90
105.4
110
33.8
40
36.0
40
57.7
60
66.3
70
83.7
90
111.5
125
111.5
125
136.4
150
183.6
200
192.9
200
111.5
125
111.5
125
151.0
175
172.7
175
216.0
225
55.6
70
55.6
70
75.5
80
86.3
90
108.0
110
43.9
50
43.9
50
61.2
70
69.8
70
87.2
90

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wj 300Wj 240