Toshiba RAV-162BH-PE Service Manual page 37

Air-conditioner split built-in duct type, heat pump; split ceiling type, heat pump; split wall type, heat pump; split cassette type, heat pump
Table of Contents

Advertisement

4.15 RAV-262AH-PE
No.
PARTS NAME
1
Compressor
2
Outdoor unit fan motor
Running capacitor for
3
outdoor
fan motor
4
Magnetic contactor
5
High pressure switch
Soleniod coil for four-way
6
valve
7
Crankcase heater
8
Sensor for defrosting
9
Fuse
10 Sensor for cooling operation
in low ambient temperature
11 Bimetal thermostat
12 Solenoid coil for two-way
valve
13 Transformer for outdoor unit
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
TYPE
PH330X3-4MS Output (Rated) 2.2 kW, 2 pole, 3 phase, 220/240V,
SMF-230-63N-2 Output (Rated) 63W, 6 pole, 1 phase, 230V, 50Hz
EEP2G405HQ
FMca-1S
ACB-2TBO4W
CHV-AC240V
CS-7
NEV202DXF
FT-67
-37-
www.heronhill.co.uk
SPECIFICATIONS
50Hz
AC 400V, 4µF
AC 220~240V, 50Hz
Tripping pressure 30kg/cm²G
pressure 23kg/cm²G
AC 220~240V
AC 240V, 28W
Maximum input
15.5mA
5A
Maximum input
15.5mA
Tripping temp: 110°C
90°C
AC 220-240V, 50Hz
AC 187~264V
Resetting
°C
–12
10
K
W
67.5
21.3
°C
–12
10
K
W
67.5
21.3
Resetting temp:
Fax: 01823 665807

Hide quick links:

Advertisement

Table of Contents
loading