Displaying/Modifying Control Parameters/Settings Report - Wolf COB Installation Instructions And Technical Manual

Boiler for heating boiler with stratification cylinder oil condensing boiler
Table of Contents

Advertisement

The control parameters can only be modified or displayed via Wolf control accessories with eBUS capability. For installation
and procedures, check the operating instructions of the relevant accessories.
BM programming module
L.h. rotary selector -
program selection
Display
Info key
Single cylinder
heating key
Parameter overview / settings report
(settings and functions on the following pages)
Parameter
A09
Frost protection limit
A10
Parallel DHW operation
A14
Maximum DHW temperature
HG00
Matching the pipe length
HG01
Burner switching differential
HG06
Pump operating mode
HG07
Boiler circuit pump run-on time
HG08
Maximum limit, boiler circuit TV-max.
HG09
Burner cycle block
HG13
Programmable input E1
HG14
Programmable output A1
HG15
Cylinder hysteresis
HG16
N / A
HG17
N / A
HG19
Cylinder primary pump run-on time
HG20
Maximum cylinder heating time
HG21
Minimum boiler water temperature TK-min.
HG22
Maximum boiler water temperature TK-max.
HG25
Boiler overtemperature during DHW cylinder heating
HG28
Burner operating mode
HG31
Blocking time burner stage 2
Pressing the r.h. rotary selector leads to control level 2, where you can select the menu levels shown in the overview by turning
the rotary selector clockwise.
Pressing the Info key takes you back to the standard display, irrespective of which submenu is currently displayed.
The system automatically also returns to the standard display when no adjustment is made for more than one minute.
All available set and actual temperatures, burner starts and hours run as well as other system values can be displayed. This scan
is identical to that initiated via the Info key.
24
18. Displaying / modifying control parameters
R.h. rotary selector -
temperature selection
Heating key
Setback key
Modifications must only the carried out by a
NB
recognised heating contractor or by the Wolf
customer service.
To prevent damage to the heating system, cancel
night setback when outside temperatures fall
below -12 °C. If this rule is not observed, ice
may build up on the flue outlet which may cause
injury or material losses.
A:
- System parameters
HG: - Boiler parameters
Setting range
Factory setting Individual settings
-20 to +10 °C
+2 °C
0 / 1
60 to 80 °C
65 °C
1 to 5
1 to 20 K
0 to 3
0 to 30 min
4 min
40 to 90 °C
75 °C
1 to 30 min
10 min
1 to 11
0 to 14
1 to 30 K
0 to 10 min
5 min
0 to 5 h
20 to 90 °C
20 °C
50 to 90 °C
80 °C
0 to 40 K
1 to 5
0 to 40 min
10 min
0
3
10 K
0
1
0
5 K
2 h
10 K
2
3062547_201507