Wolf COB Installation Instructions And Technical Manual page 51

Boiler for heating boiler with stratification cylinder oil condensing boiler
Table of Contents

Advertisement

Vertical concentric balanced flue C33x (examples) system DN 80/125 and DN 110/160
1 Oil condensing boiler
2 Connection adaptor with test nipple
for air and flue gas (included in COB
standard delivery)
3 Balanced flue incl. inspection aperture
(250 mm long)
4 Balanced flue DN 80/125
500 mm
1000 mm
2000 mm
5 Spacer clip
6 Mounting bracket
for roof outlet
7 Balanced flue, vertical
(roof outlet for flat
or pitched roofs)
8 Separator
(slide coupling), if required
9 45° bend
10 Inspection tee, 87°
11 87° bend
12 Universal tile for
pitched roof 25° - 45°
13 "Klöber" adaptor 20° - 50°
14 Flat roof collar
3062547_201507
31. Design information
7
6
4
5
4
3
2
1
C33x
Please note: Install the horizontal flue with approx. 3° fall (6 cm/m) towards
the boiler. During installation, slide the separator (8) fully
into the coupling. Push the next balanced flue (4) 50 mm
(dim. "S") into the coupling of the separator, and secure in
this location, e.g. with pipe clips DN 125 (5) or a fixing screw
on the air side.
Lubricate the pipe ends and gaskets for easier installation
(use only grease without silicone).
Determine the required inspection piece (3) (10) with your
NB
local flue gas inspector prior to installation.
7
6
12
13
6
14
3
9
4
9
4
5
S
S
8
10
3
2
2
1
1
C33x
C33x
7
6
5
4
8
4 5
11
51