Install the balanced flue distributor eccentrically (29) for
separate balanced flue on the oil condensing boiler.
Install the horizontal flue with approx. 3° fall (6 cm/m) towards
the boiler. Route the horizontal air supply with a 3° fall towards
the outside – install the air inlet with a cowl; permissible wind
pressure at the air inlet 90 Pa. The burner will not operate with
higher wind pressure.
Balanced flue routing, open flue B33 and B23
(examples) DN 80/125 and DN 110/160
1 Oil condensing boiler
2 Connection adaptor with test nipple
for air and flue gas (included in COB standard delivery)
4 Balanced flue
500 mm
1000 mm
2000 mm
5 Spacer clip (only if required)
10 Inspection tee 87°
16 Rose
22 Connection to
flue gas chimney B33
length 250 mm with air aperture
23 Support rail
24 87° support bend
25 Spacer
26 PP flue
500 mm
1000 mm
2000 mm
27 Cowl
29 Balanced flue distributor
80/80 mm
30 Air inlet pipe
31 87° bend
32 Tee 87° with
inspection aperture
33 PP outlet
52
31. Design information
16
approx.1500 mm
16
30
31
32
33
29
2
1
Secondary
ventilation
C53
4
5
10
2
1
Secondary
ventilation
B33
32
2
1
B23
27
33
26
26
16
24
23
27
33
26
22
16
25
24
23
27
33
26
26
16
25
24
23
Secondary
ventilation
3062547_201507

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cob-ts

Table of Contents