Displaying / Modifying Control Parameters - Wolf CGB-75 Installation And Technical Manual

Wall mounted gas boiler
Table of Contents

Advertisement

Modifications must only the carried out by
NB
a recognised heating contractor or by Wolf
customer service.
Incorrect operation can lead to system faults.
NB
Please note when adjusting parameter GB05 /
A09 (frost protection / outside temperature), that
frost protection is no longer safeguarded if you
set temperatures lower than 0 °C. This can lead
to heating system damage.
The control parameters can be modified or displayed via control accessories with eBUS capability. For procedures, check the
operating instructions of the relevant accessories.
Column 1 settings apply to control accessories ART, AWT
Column 2 settings apply to Wolf control system with BM programming module
1
2
Parameter
GB01
HG01
Burner switching differential
HG02
Low end fan speed
Minimum fan speed in %
HG03
High end fan speed WW
Maximum fan speed for DHW in %
GB04
HG04
High end fan speed HZ
Maximum fan speed for heating in %
GB05
A09
Frost protection, outside temperature
With connected outside temperature sensor and insufficient
temperature pump ON
GB06
HG06
Pump operating mode
0 -> Pump ON in winter mode
1 -> Pump ON during burner operation
GB07
HG07
Boiler circuit pumps run-on time
Heating circuit pump run-on time in minutes in heating mode
GB08
HG08 or
Maximum limit, boiler circuit TV-max
HG22
Applicable to heating operation
GB09
HG09
Burner cycle block
Applicable to heating operation
HG10
eBUS address
Heat source BUS address
HG11
DHW quick start
Temperature of the plate heat exchanger in summer mode
(only applicable to combi boilers)
HG12
Gas type
Not supported
Programmable input E1
GB13
HG13
Various functions can be allocated to input E1. See chapter
"Connection input E1"
GB14
HG14
Programmable output A1
Output A1 (230 V AC)
Various functions can be allocated to output A1. See
chapter "Connection output A1"
GB15
HG15
Cylinder hysteresis
Switching differential during cylinder re-heating
HG21
Minimum boiler water temperature TK-min
30 62 555_0709

Displaying / modifying control parameters

To prevent damage to the heating system, cancel
night setback when outside temperatures fall
below - 12 °C. If this rule is not observed, ice
may build up on the flue outlet which may cause
injury or material losses.
You can find the output data for the boiler on
the type plate.
Unit
Factory setting
K
8
%
CGB-75:30
CGB-100:25
%
CGB-75:100
CGB-100:100
%
CGB-75:100
CGB-100:100
°C
2
0
min.
1
°C
80
min.
7
0
°C
10
0
1
Room
thermostat
6
Cylinder
primary pump
5
°C
20
min.
max.
5
30
30
100
25
100
30
100
25
100
30
100
25
100
-10
10
0
1
0
30
40
90
1
30
0
5
10
60
0
1
0
5
0
9
1
30
20
90
27