General Data / Specifications - LG MULTI F Engineering Manual

Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

F
MULTI
FOUR-WAY CEILING-CASSETTE INDOOR UNITS
F
MULTI
MAX
Table 71:Multi F Four-Way Ceiling-Cassette Indoor Unit General Data.
Model Name
Nominal Cooling Capacity (Btu/h)
Nominal Heating Capacity (Btu/h)
Operating Range
Cooling (°F WB)
Heating (°F DB)
Fan
Type
Motor Output (W) x Qty.
Motor/Drive
Airflow Rate CFM (H/M/L)
Unit Data
Refrigerant Type
2
Refrigerant Control
Power Supply V, Ø, Hz
3
Rated Amps (A)
Sound Pressure Level ±3 dB(A) (H/M/L)
Body Dimensions (W x H x D, in.)
Grille (PT-UQC, sold separately) Dimensions (WxHxD, in.)
Body Net Weight (lbs.)
Grille (PT-UQC, sold separately) Net Weight (lbs.)
Body Shipping Weight (lbs.)
Grille (PT-UQC, sold separately) Shipping Weight (lbs.)
Power Wiring / Communications Cable (No. x AWG)
Heat Exchanger (Row x Column x Fin / inch) x Number
Piping
Liquid (in.)
Vapor (in.)
Drain O.D. / I.D. (in.)
Nominal capacity is rated 0 ft. above sea level with a 0 ft. level difference between outdoor and indoor
1
units. All capacities are net with a combination ratio between 95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
This unit comes with a dry helium charge.
2
LMCN077HV
7,000
1
8,100
1
265 / 212 / 177
31 / 27 / 24
4
5
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

General Data / Specifications

LMCN097HV
9,000
10,400
Brushless Digitally Controlled / Direct
300 / 265 / 230
208-230, 1, 60
36 / 33 / 30
22-7/16 x 8-7/16 x 22-7/16
27-9/16 x 7/8 x 27-9/16
31
34
36
11
(2 x 8 x 18) x 1
1/4
3/8
Acceptable operating voltage: 187V-253V.
3
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
4
same in both cooling and heating mode. These values can increase due to ambient conditions during
operation.
All power wiring / communications cables to be minimum 18 AWG, 4-conductor, stranded, shielded,
5
and must comply with applicable local and national codes.
LMCN125HV
LMCN185HV
12,000
18,000
13,800
20,800
57-77
59-81
Turbo
43 x 1
335 / 283 / 247
459 / 424 / 388
R410A
EEV
0.25
38 / 35 / 32
38 / 37 / 34
22-7/16 x 10-3/32 x 22-7/16
7
40
4 x 18
(2 x 10 x 18) x 1
1-1/4, 1
CEILING-CASSETTE | 131
34
42
11
1/4
1/2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents