Table 4: Ducted High Static M2 Indoor Unit General Data.
Model No.
Cooling Mode Performance
Capacity (Btu/h)
Max Power Input
(W)
1
L/M/H Power Input at Factory Default (W)
Heating Mode Performance
Capacity (Btu/h)
Max Power Input
(W)
1
L/M/H Power Input at Factory Default (W)
Entering Mixed Air
Cooling Max. (°F WB)
Heating Min. (°F DB)
2
Unit Data
Refrigerant Type
3
Refrigerant Control
Sound Power
dB(A) (H-M-L, @0.24" ESP)
4
Sound Pressure
dB(A) (H/M/L, @0.24" ESP)
5
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cable
(No. x AWG)
6
Fan
Type
Motor
Housing
Motor/Drive
Airflow Rate H / M / L (CFM)
High Mode (Factory Set)
External Static Pressure (in. wg)
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.)
Vapor Line (in., O.D.)
Condensate Line (in., I.D.)
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes.
This unit comes with a dry nitrogen charge.
All capacities are net with a combination ratio between 95-105%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice. Current certified ratings are available at www.ahridirectory.org.
Max. power input is rated at maximum setting value.
1
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air
2
Source Units produced after February 2019.
ARNU073M2A4
7,500
430
21 / 29 / 38
8,500
430
21 / 29 / 38
76
59
R410A
EEV
42 / 41 / 41
38 / 37 / 36
82.9
95.5
2 x 18
Sirocco
1
2
468 / 381 / 294
0.24
1/4 Flare
1/2 Flare
1
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Specifications − High-Static M2 Chassis
ARNU093M2A4
ARNU123M2A4
9,600
12,300
430
430
21 / 29 / 38
25 / 34 / 43
10,900
13,600
430
430
21 / 29 / 38
25 / 34 / 43
76
76
59
59
R410A
R410A
EEV
EEV
42 / 41 / 41
42 / 41 / 41
38 / 38 / 36
38 / 38 / 36
82.9
82.9
95.5
95.5
2 x 18
2 x 18
Sirocco
Sirocco
1
1
2
2
Brushless Digitally Controlled / Direct
468 / 381 / 294
512 / 425 / 337
0.24
0.24
1/4 Flare
1/4 Flare
1/2 Flare
1/2 Flare
1
1
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
3
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
Sound Power level is measured using rated conditions, and tested in a reverberation room
4
per AHRI 260.
5
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, twisted, stranded, shielded
6
and must comply with applicable local and national codes. Ensure the communication
cable is properly grounded at the main outdoor unit only.
communication cable at any other point.

GENERAL DATA

ARNU153M2A4
ARNU183M2A4
15,400
430
25 / 34 / 43
34 / 43 / 67
17,100
430
25 / 34 / 43
34 / 43 / 67
76
59
R410A
EEV
42 / 42 / 41
44 / 42 / 42
38 / 38 / 36
39 / 38 / 37
82.9
95.5
2 x 18
Sirocco
1
2
512 / 425 / 337
673 / 512 / 425
0.24
1/4 Flare
1/4 Flare
1/2 Flare
1/2 Flare
1
Do not ground the ODU-IDU
19,100
430
21,500
430
76
59
R410A
EEV
82.9
95.5
2 x 18
Sirocco
1
2
0.24
1
13

Advertisement

Table of Contents
loading