Power Wiring / Communications Cable Guidelines
• Follow manufacturer's circuit diagrams in the technical manuals.
• Confirm power source specifications.
• Confirm that the electrical capacity is sufficient.
• Starting current must be maintained ±10 percent of the rated current marked on the outdoor unit name plate.
• Confirm cable thickness specifications.
• It is recommended that a circuit breaker is installed, especially if conditions could become wet or moist.
• Include a disconnect in the power wiring system, add an air gap contact separation of at least 1/8 inch in each active (phase) conductor.
• Loose wiring may cause unit malfunction, or the terminal to overheat and catch fire.
• Terminal screws may become loose during transport. Properly tighten the terminal connections during installation.
A voltage drop may cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Connecting the Power Wiring and Communications Cable
1. Insert the power wiring / communications cable from the out-
door unit or branch distribution unit (Multi F MAX systems only)
through the bottom of the indoor unit.
2. Connect each wire to its appropriate terminal on the indoor unit
control board. Verify that the color and terminal numbers from
the outdoor unit or branch distribution unit (Multi F MAX systems
only) wiring match the color and terminal numbers on the indoor
unit.
3. Secure the power wiring / communications cable with the cable
restraint.
Figure 29:Simplified View of Indoor Unit to Outdoor Unit / Branch
Distribution Unit Terminal Connections—LMAN097HVT and
LMAN127HVT models.
GND
Indoor Unit Terminal Block
1(L1)
2(L2)
3(C)
Figure 30:Simplified View of Indoor Unit to Outdoor Unit / Branch
Distribution Unit Terminal Connections—LMAN187HVT models.
GND
Indoor Unit Terminal Block
1(L1 ) 2(L2)
3
ART COOL MIRROR INDOOR UNITS
Outdoor Unit Terminal Block or
Branch Distribution Unit Terminal Block
(Multi F MAX Systems Only)
3 or S
GND
Outdoor Unit Terminal Block or
Branch Distribution Unit Terminal Block
(Multi F MAX Systems Only)
3 or S
4
GND
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Installation and Best Layout Practices
Figure 28:Connecting the Power Wiring / Communications Cable.
Terminal block
Wired Remote Controller
Terminal (Optional)
Power wiring /
communications cable
Cable restraint
ART COOL MIRROR | 33