Factory Supplied Parts And Materials / Installation - LG MULTI F Engineering Manual

Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

DUCT (HIGH STATIC) INDOOR UNITS

Factory Supplied Parts and Materials / Installation

Factory Supplied Parts
Table 62: Parts Table.
Part
Quantity
Drain Hose
One (1)
Metal Clamp
Two (2)
Washers for
Hanging
Eight (8)
Brackets
Simple Mode Controllers for the ceiling-concealed duct (high static) indoor units are also referenced by Model No. PQRCVCL0QW.
1
Factory Supplied Materials
• Owner's Manual
• Installation Manual
• Read all instructions before installing the product.
• Installation work must be performed by authorized personnel and in accordance with the national wiring standards and all local
codes.
Selecting the Best Location
Do's
• Place the unit where air circulation will not be blocked.
• Place the unit where drainage can be obtained easily.
• Place the unit where noise prevention is taken into consideration.
• Ensure there is sufficient strength to bear the load of the indoor unit.
• Ensure there is sufficient maintenance space.
• Locate the indoor unit in a location that is level, and where it can be easily connected to the outdoor unit / branch distribution unit.
Don'ts
• The unit should not be installed near a heat or steam source, or where considerable amounts of oil, iron powder, or flour are used.
• The unit should not be installed where sulfuric acid and flammable or corrosive gases are generated, vented into, or stored.
• Avoid installing the unit near high-frequency generators or near any equipment that generates an electromagnetic field (minimum 3-1/3
feet away).
• Do not install the unit near a doorway.
The unit may be damaged, may malfunction, and / or will not operate as designed if installed in any of the conditions
listed.
120 | DUCT (HIGH STATIC)
Image
Insulation for
(AKB72955816)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Part
Quantity
Zip Ties
Four (4)
One (1) Set
Fittings
Simple
Controller
with Mode
One (1)
Selection
1
Required Tools
• Level
• Screwdriver
• Electric drill
• Hole core drill
• Flaring tool set
F
MULTI
F
MULTI
Image
For Vapor Piping For Liquid Piping
• Torque wrenches
• Hexagonal wrench
• Gas-leak detector
• Thermometer
MAX

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents