LG MULTI F Engineering Manual page 52

Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

ART COOL GALLERY INDOOR UNITS
Installation and Best Layout Practices
Power Wiring / Communications Cable Guidelines
• Follow manufacturer's circuit diagrams in the technical manuals.
• Confirm power source specifications.
• Confirm that the electrical capacity is sufficient.
• Starting current must be maintained ±10 percent of the rated current marked on the outdoor unit name plate.
• Confirm cable thickness specifications.
• It is recommended that a circuit breaker is installed, especially if conditions could become wet or moist.
• Include a disconnect in the power wiring system, add an air gap contact separation of at least 1/8 inch in each active (phase) conductor.
• Loose wiring may cause unit malfunction, or the terminal to overheat and catch fire.
• Terminal screws may become loose during transport. Properly tighten the terminal connections during installation.
A voltage drop may cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Connecting the Power Wiring and Communications Cable
1. Insert the power wiring / communications cable from the out-
door unit or branch distribution unit (Multi F MAX systems only)
through the access hole of the indoor unit (ground wire should be
longer than the other wires / cables). Unscrew the control board
cover.
2. Connect each wire to its appropriate terminal on the indoor unit
control board. Verify that the color and terminal numbers from
the outdoor unit or branch distribution unit (Multi F MAX systems
only) wiring match the color and terminal numbers on the indoor
unit.
3. Secure the power wiring / communications cable to the control
board.
4. Reattach the control board cover.
Figure 62:Simplified View of Indoor Unit to Outdoor Unit / Branch
Distribution Unit Terminal Connections—LMAN097HVP and
LMAN127HVP models.
GND
Indoor Unit Terminal Block
1(L1)
2(L2)
3(C)
52 | ART COOL GALLERY™
Outdoor Unit Terminal Block or
Branch Distribution Unit Terminal Block
(Multi F MAX Systems Only)
3 or S
GND
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 61:Connecting the Power Wiring / Communications Cable.
Control Board Cover
Lock nut
(field supplied)
Conduit
(field supplied)
F
MULTI
F
MULTI
MAX
1(L1) 2(L2)
3