Troubleshooting Without The Display - Worcester CDi Combi N.G Service Booklet

Floor mounted and wall hung rsf gas fired condensing boilers
Table of Contents

Advertisement

9.2

TROUBLESHOOTING WITHOUT THE DISPLAY

Fault
Cause
Required room
Thermostatic valve(s) set too low.
Flow temperature controller on the boiler set
temperature not
too low.
achieved.
Air in the heating system.
Holiday key on the boiler enabled.
Required room
Radiators become too hot.
temperature greatly
FR 110 installed in an unfavourable location,
exceeded.
e.g. external wall, near windows, in a
draught,
Excessive room
Temporary influence of external heat on the
temperature
room, e.g. through radiant energy from the
fluctuations.
sun, lighting, TV, fireplace etc.
Temperature rises
Clock time incorrectly set.
instead of falling.
Room temperature
The building retains a lot of heat.
too high during
"Economy" and/or
"Frost" mode.
Incorrect or no
BUS connection or BUS subscriber faulty.
control.
Controller can only
Mode selector faulty.
be set to automatic
mode.
Hot water cylinder
Hot water temperature control on boiler set
does not heat up.
too low.
Flow temperature controller on the boiler set
too low.
Hot water programme fault.
Incorrect System configuration for hot water
system.
Heating on during
Heat-up optimisation starts the heating early
the night.
so that the home reaches the desired room
temperature by the set time.
Tab. 33
8 716 115 748 (2009/09)
Supplied By www.heating spares.co Tel. 0161 620 6677
TROUBLESHOOTING - FR110
Remedy
Set thermostatic valve(s) higher.
Set the flow temperature controller higher.
Reduce influence of solar optimisation if
necessary.
Bleed radiators and vent the heating system.
Disable the holiday key on the boiler.
Set thermostatic valve(s) lower.
Set Heating levels for "Comfort" lower.
Select a better location for FR 110 and
reposition it.
Select a better location for FR 110 and
reposition it.
Check time setting.
Set an earlier switching time for "Economy"
and/or "Frost".
Check the BUS connection against the wiring
diagram and correct it if required.
Have FR 110 replaced by your heating engineer.
Set hot water temperature control higher.
Reduce influence of solar optimisation if
necessary.
Turn the flow temperature control on the boiler
clockwise as far as it will go.
Check/correct programme.
Correct the configuration to match the hot
water system connected.
Set a later time for the desired room
temperature.
Switch off heat-up optimisation.
67