Omron CJ2 User Manual page 325

Cj series
Hide thumbs Also See for CJ2:
Table of Contents

Advertisement

Error
Error flag
Error
code
(Auxiliary
(inA400)
Too Many I/O
0x80E1
A401.11: Too
Points Error
Many I/O
Points Flag
Unit/Rack
0x80E9
A401.13: Dupli-
Number
cation Error
Duplication
Flag
Error
0x80EA
CJ2 CPU Unit Hardware User's Manual
Flag and
word data
Area)
A407.13 to
One of the following values exceeds
A407.15: Too
the maximum or is allocated to more
Many I/O
than one Unit.
Points, Details
1.
The total number of I/O points
1, 2
set in the I/O tables exceeds the
maximum allowed for the CPU
Unit (bits: 000)
2.
There are more than 32 interrupt
inputs (bits: 001).
3.
The number of Expansion Racks
exceeds the maximum (bits:
101).
4.
More than 10 I/O Units are con-
nected to one Rack (bits: 111).
A410: CPU
The same number has been allo-
Bus Unit
cated to more than one CPU Bus
Duplicated
*5
Unit.
Number Flags
A411 to A416:
The same number has been allo-
Special I/O
cated to more than one Special I/O
Unit Dupli-
*6
Unit.
cated Num-
ber Flags
A409: Expan-
The same I/O word has been allo-
sion Rack
cated to more than one Basic I/O
Duplicated
Unit.
Rack Number
An Expansion Rack's starting word
address exceeds CIO 0901.The cor-
responding bit in A409.00 to A409.03
(Racks 0 to 3) will be turned ON.
Probable cause
Correct the problem and then turn the power supply
OFF and back ON.
*4
Check the unit numbers, eliminate the duplications,
and turn the Rack's power supply OFF and then ON
again.
Check the unit numbers, eliminate the duplications,
and turn the Rack's power supply OFF and then ON
again.
Check allocations to Units on the rack number
whose bit is ON in A409.00 to A409.03. Correct the
allocations so that no words are allocated more than
once, including to Units on other Racks, and turn the
Rack's power supply OFF and then ON again.
Check the first word setting for the Rack indicated in
A409.00 to A409.03 and change the setting to a
valid word address below CIO 0900 with a Program-
ming Device (such as a CX-Programmer).
Appendices
Possible remedy
A-95