Terminal Connections
*1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the
response times are set to 0 ms due to internal element delays.
Note Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage does not exceed the ON voltage (19 V) plus the residual volt-
age of the sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
CJ1W-IA201 AC Input Unit (200 VAC, 8 Points)
Name
Model
Rated Input Voltage
Rated Input Voltage Range
Input Impedance
Input Current
ON Voltage/ON Current
OFF Voltage/OFF Current
ON Response Time
OFF Response Time
Number of Circuits
Number of Simultaneously ON Points
Insulation Resistance
Dielectric Strength
Internal Current Consumption
CJ2 CPU Unit Hardware User's Manual
CN1
Signal
Connec-
Allocated
Signal
tor pin
name
CIO word
name
IN0
IN8
40
39
IN1
IN9
38
37
24 VDC
IN2
IN10
36
35
IN3
IN11
34
33
IN4
IN12
32
31
IN5
IN13
30
29
IN6
IN14
28
27
IN7
IN15
26
25
COM0
COM0
24
23
NC
NC
22
21
IN0
IN8
20
19
IN1
IN9
18
17
IN2
IN10
16
15
IN3
IN11
14
13
IN4
IN12
12
11
IN5
IN13
10
9
IN6
IN14
8
7
IN7
IN15
6
5
COM1
COM1
4
3
NC
NC
2
1
24 VDC
• The input power polarity can be
connected in either direction.
• Be sure to wire both pins 23 and
24 (COM0) of CN1, and set the
same polarity for both pins.
• Be sure to wire both pins 3 and 4
(COM1) of CN1, and set the same
polarity for both pins.
8-point AC Input Unit with Terminal Block
CJ1W-IA201
200 to 240 VAC 50/60 Hz
170 to 264 VAC
21 kΩ (50 Hz), 18 kΩ (60 Hz)
9 mA typical (at 200 VAC, 50 Hz),
11 mA typical (at 200 VAC, 60 Hz)
120 VAC min./4 mA min.
40 VAC max./2 mA max.
18.0 ms max. (PLC Setup default setting: 8 ms)
48.0 ms max. (PLC Setup default setting: 8 ms)
8 (8 points/common, 1 circuit)
100% (8 points/common) simultaneously ON
20 MΩ between external terminals and the GR terminal (500 VDC)
2,000 VAC between the external terminals and the GR terminal for
1 minute at a leakage current of 10 mA max.
80 mA max.
CN2
Allocated
Allocated
Signal
Connec-
CIO word
CIO word
tor pin
name
24 VDC
NC
1
2
COM3
3
4
IN15
5
6
IN14
7
8
IN13
9
10
IN12
11
12
IN11
13
14
IN10
15
16
IN9
17
18
IN8
19
20
NC
21
22
COM2
23
24
IN15
25
26
IN14
27
28
IN13
29
30
IN12
31
32
IN11
33
34
IN10
35
36
24
VDC
IN9
37
38
IN8
39
40
• The input power polarity can be con-
nected in either direction.
• Be sure to wire both pins 23 and 24
(COM2) of CN2, and set the same polar-
ity for both pins.
• Be sure to wire both pins 3 and 4 (COM3)
of CN2, and set the same polarity for
both pins.
Appendices
Allocated
Signal
CIO word
name
NC
COM3
IN7
IN6
IN5
IN4
IN3
IN2
IN1
IN0
NC
COM2
IN7
IN6
IN5
IN4
IN3
IN2
IN1
IN0
*1
*1
A-11