SiENBE04-808_A
3.3
Controls at Mode Changing / Start-up
3.3.1 Preheating Operation
Outline
The inverter operation in open phase starts with the conditions of the preheating command from
the indoor unit, the outdoor temperature, and the discharge pipe temperature.
RK(X)S20-42G2V1B, ARXS20-42G2V1B
Detail
ON Condition
When the discharge pipe temperature is below 10ºC, the inverter operation in open phase
OFF Condition
When the discharge pipe temperature is higher than 12ºC, the inverter operation in open
RK(X)S20-35G2V1B9, ARXS20-35G3V1B
Outdoor temperature ≥ 7°C → Control A
Outdoor temperature < 7°C → Control B
Control A
ON condition
OFF condition
Control B
ON condition
OFF condition
RK(X)S50G2V1B, ARXS50G2V1B
Outdoor temperature ≥ 10°C → Control A
Outdoor temperature < 10°C → Control B
Control A
ON condition
OFF condition
Control B
ON condition
OFF condition
Function and Control
starts.
phase stops.
Discharge pipe temperature < 10°C
Discharge pipe temperature > 12°C
Radiation fin temperature ≥ 90°C
Discharge pipe temperature < 20°C
Discharge pipe temperature > 22°C
Radiation fin temperature ≥ 90°C
Discharge pipe temperature < 6°C
Discharge pipe temperature > 8°C
Radiation fin temperature ≥ 90°C
Discharge pipe temperature < 10.5°C
Discharge pipe temperature > 12°C
Radiation fin temperature ≥ 90°C
Control Specification
48