Ol Activation (Compressor Overload) - Daikin FTXS20G2V1B Service Manual

G-series
Hide thumbs Also See for FTXS20G2V1B:
Table of Contents

Advertisement

SiENBE04-808_A
4.9

OL Activation (Compressor Overload)

E5
Remote Control
Display
Method of
A compressor overload is detected through compressor OL.
Malfunction
Detection
„ If the error repeats twice, the system is shut down.
Malfunction
„ Reset condition: Continuous run for about 60 minutes without any other error
Decision
∗ The operating temperature condition is not specified.
Conditions
„ Defective discharge pipe thermistor
Supposed
„ Defective electronic expansion valve or coil
Causes
„ Defective four way valve or coil
„ Defective outdoor unit PCB
„ Refrigerant shortage
„ Water mixed in refrigerant
„ Defective stop valve
Troubleshooting
Check No.04
Refer to P.146
Check No.05
Refer to P.147
Check No.06
Refer to P.148
Check No.11
Refer to P.150
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Discharge pipe
thermistor disconnected?
NO
Check No. 06
Check the thermistors.
OK
Check No. 04
Check the electronic
expansion valve.
OK
Check No. 05
Check the four way valve.
OK
Check No. 11
Check the refrigerant line.
OK
YES
NG
∗ Discharge pipe thermistor
NG
NG
NG
∗ Refrigerant shortage
∗ Water mixed
∗ Stop valve
Troubleshooting
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the electronic
expansion valve or the coil.
Replace the four way valve
or the coil.
Replace the outdoor unit
PCB.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R11999)
114

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents