Clearance To Combustibles; Mantels; Mantel Leg Chart; Hearth - Majestic 360DVS2 Installation Instructions & Homeowner's Manual

Multisided top/rear vent convertible direct vent majestic products, 360dvs series
Table of Contents

Advertisement

Vermont Castings, Majestic Products, 360DVS Series

Clearance to Combustibles

Appliance
Top
Bottom
Vent End
Nonvent End (DVS2)
Venting
Concentric sections of DV Vent:
Top, bottom & sides
Nonconcentric sections of DV Vent:
Side and bottom
Top

Mantels

The height at which a combustible mantel is fitted
above the fireplace is dependent on the depth of the
mantel. This also applies to the distance between the
mantel leg (if so fitted) and the fireplace. For correct
mounting height and width, refer to Fig. 2a and 2b and
the Mantel Chart below.
The fitting of a bay window trim kit does not affect the
distances and reference points referred to in the
diagram and chart.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using paint or lacquer to finish the mantel, such
paint or lacquer must be heat resistant to prevent
discoloration.
V
W
X
Y
Z
A
B
C
D
E
Bottom of Door Trim
Mantel Chart
Mantel Shelf
Ref.
or Breast Plate
V
10" (254 mm)
W
8" (203 mm)
X
6" (152 mm)
Y
4" (102 mm)
Z
2" (51 mm)
Fig. 4a Combustible mantel minimum installation
8
0" (0 mm) to standoff
0" (0 mm)
1
/
" (13 mm) to rear panel
2
0" (0 mm)
1" (25 mm)
1" (25 mm)
2" (51 mm)
Fireplace
Louvre Assembly
Top
Top of Combustion
Chamber
CFM146
Mantel from Top
Ref.
of Comb. Chamber
A
19" (483 mm)
B
17" (432 mm)
C
15" (381 mm)
D
13" (330 mm)
E
11" (297 mm)
CFM176
Top View
Front View
Side of Combustion Chamber

Mantel Leg Chart

Mantel
Ref.
Leg Depth
F
10" (254 mm)
G
8" (203 mm)
H
6" (152 mm)
I
4" (102 mm)
J
2" ( 51 mm)
Fig. 4b Combustible mantel leg minimum installation

Hearth

A hearth is not mandatory; however, for aesthetic
purposes, we recommend installing a
noncombustible hearth that projects out 12" (305
mm) or more from the front of the fireplace.
Cold climate installation recommendation:
When installing this unit against a
noninsulated exterior wall or chase, it is
mandatory the outer walls be insulated
to conform to applicable insulation
codes.
J
I
H
G
Mantel
Leg
K
L
M
N
O
Mantel Leg From Side
Ref. of Combustion Opening
1
K
11
/
" (292 mm)
2
1
L
9
/
" (241 mm)
2
1
M
7
/
" (191 mm)
2
1
N
5
/
" (140 mm)
2
O
3
1
/
" ( 89 mm)
2
10002547
F
CFM197
Mantel
Leg
CFM170
CFM166a