2.3 Flue system specifications

2.3.1 Coaxial Horizontal flue systems.
The product is supplied complete with a concentric turret assembly and standard concentric
horizontal balanced flue terminal assembly suitable for flue lengths from 200mm to 10.5m (From
flue turret to flue terminal end)
Diagram 2.2 Flue through wall
Additional components are available to extend the length of the flue ducts. These components are
as follows:-
1000 mm straight concentric flue extension (Increases the length of flue by 960 mm).
500 mm straight concentric flue extension (Increases the length of flue by 460 mm).
Air duct sealing collar (One required per joint).
Flue weather proofing seal. (two per installation)
Extension ducts can be used to increase the straight flue length up to 10.5m, is measured
between the end of the flue terminal to the turret outlet.
When measuring up for maximum flue lengths, it is generally considered that a 90
equivalent to the frictional losses experienced on a 2m flue extension, for example if two 90
elbows are used in the flue run then the total straight flue run must not exceed 6.5m.
Navien stirling engine m-CHP installation manual
0
elbow is the
11 of 88
Page No:
0