Notice!
To reset after a fire alarm, interrupt power to the receiver for a minimum of 1 sec. If the fire
panel does not allow you to reset, install a switch in series with Terminal 8.
5.2

Wiring a remote indicator

A D306 Remote Indicator Plate is shipped with the D296 as a standard accessory. The D306
has three LEDs to indicate the detector's condition and status and test points for measuring
the sensitivity voltage. Although the D306 is not required, the manufacturer recommends its
installation to check the detector's condition from ground level. If using D306 Remote
Indicator Plate, install the remote indicator connector to the receiver as indicated in the
following figure.
Bosch Security Systems, Inc.
Terminal
Description
4 and 5
On fire alarm, normally open (NO) fire alarm contacts
close (short).
6 and 7
On trouble, normally closed (NC) trouble contacts open.
8 and 9
Input power terminals. For operating voltages, see
Specifications, page 26.