Toshiba MM-A0280HT Service Manual page 86

Modular multi split type system
Hide thumbs Also See for MM-A0280HT:
Table of Contents

Advertisement

Diagnostic Procedure for Check Code
Check code
[d7]
Protection of low oil level detection
Are balancing pipe valves
of all outdoor units
fully open?
Yes
Is the compressor case oil
removal valve fully open?
Yes
Are TK1 and TK2 sensors
correctly connected?
Yes
Is there refrigerant stagnation
in compressor case?
Yes
Refrigerant
stagnation is
detected.
Check refrigerant stagnation
in compressor case, reset the
power source, and then start
the operation.
Troubleshooting
1. Balancing pipe valve (all outdoor units in the
connecting line) closed
2. Compressor case oil removal valve closed
3. Miswiring of TK1 sensor/TK2 sensor
4. Refrigerant stagnation in compressor case
5. SVA3, SV3B, SV3C valves error
6. Blockage in oil return circuit of oil separator
7. Blockage in oil tank circuit
No
No
No
(*1) Is there a 2-way valve
No
leakage (SV3A, SV3C) or
blockage (SV3B)?
No Leakage/Blockage
(*2) Is there a blockage in the
oil return circuit of oil separator
(Capillary, strainer)?
No blockage
Is there blockage in 2-way
valve of all outdoor units in the
connecting line (SV3A, SV3C)?
No blockage
Replace oil tank circuit.
87
Operation cause
Open balancing pipe valve fully,
reset power supply, and start
the operation.
Open compressor case oil
removal valve fully,reset
power supply, and start the
operation.
Check connector
[
Pd sensor: CN516
Ps sensor: CN515
Yes
Replace defective part.
Yes
Replace defective part.
Yes
Replace defective part.
]